With LF.3 you can preselect a divider for the signals of the incremental
encoder output (X5). The adjusted value is valid after a power-on-
reset.
Unit:
1
Value range:
1...128
Factory setting:
1
Divider Incremental
Encoder Output
8. Parameter
Description
No divider possible with resolver connection (1 : 1)!
With parameter LF. 4 you can select, if it is an asynchronous motor
or a three-phase synchronous servo motor. LF.4 releases the
adjusted motor parameter for the selected motor and does
independently a Power-On-Reset.
Unit:
1
Value range:
0:ASM / 1:SSM
Factory setting:
0:ASM
Adjustment value:
in accordance with type of the motor
With LF. 5 travel direction can be changed.
LF. 5
X2.3
X2.4
Speed setpoint
Inverter status
OFF
1
0
n_set > 0
Fxxx
OFF
0
1
n_set < 0
rxxx
ON
1
0
n_set < 0
rxxx
ON
0
1
n_set > 0
Fxxx
Unit:
1
Value range:
0:off / 1:on
Factory setting:
0:off
Adjustment value:
in accordance with the direction of travel
ASM-Rated Motor Power
Unit:
kilowatt
Value range:
0,00...75,00 kW
Factory setting:
4,00 kW
Adjustment value:
in accordance with the motor name plate
Reverse Direction of Travel
ASM/SSM-Selection