GB 48
GB
Unit:
1
Value range:
0 … 5
Factory setting:
3
Adjusted value:
according to speed real value smoothing
Speed Scan Rate
Do not change the parameter!
Unit:
1
Value range:
0 … 255
Factory setting:
0
Adjusted value:
according to real speed fluctuations
Reso-Error-Trimming
Do not change the parameter!
8. Parameter Description
When the drive system starts-up (inverter & motor) for the first
operating, the position of the encoder to the rotor position of the motor
must be known.
By input of 1 into LF.b5 the system position trimming will start. The
drive may not be loaded. The ropes must be picked off from the
sheave!
The trimming makes several function steps which where displayed
in parameter LF.b5.
Value Significance
0
no position trimming is done
1
preset drive command
2
automatic voltage increase until rated current is flowing
(Motor is set in pole position)
3
Rotation presetting control
4
store system position
5
cancel drive command
6
Power-On-Reset
7
System position has finnished
The system position is displayed and stored in LF.b2.
Summary of Contents for COMBIVERT F4-F
Page 65: ...ANTRIEBSTECHNIK...