Evaporator wiring – Heater
Strip the ends of the wires being
used for heater control.
The heater wires can be attached
to the terminal block using either
screw down terminals or spade
connectors.
17
Remove defrost termination
(Klixon®) from circuitry
Attach the black wire with orange
stripe to the L1/Line. This wire will
be connected to COM of defrost re-
lay on the controller.
Attach the orange wire with the
black stripe to the NO terminal
on the Defrost Relay to one of each
of the defrost leads.
Connect L2/Neutral to the remain-
ing defrost leads.
The defrost safety should not be re-
moved from the circuit. Its purpose
is to prevent the heaters from over
heating and causing damage.
18
© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Evaporator wiring – Liquid Line
Solenoid /Compressor
Strip the ends selected to control
the liquid line solenoid.
Attach the black wire with the yel-
low stripe to the L1. This wire will
be connected to the COM of the
L.L. Solenoid/Compressor.
Attach the yellow wire with
black stripe connects to the NO
terminal on the L.L. Solenoid/
Compressor relay to a solenoid
lead
Connect L2/Neutral to the remain-
ing L.L. Solenoid/Compressor lead.