Defrost (Heater) Relay
Strip the end of the 2 wires used for the defrost control.
Locate (2) 90° female spade connectors in the accessories kit.
Crimp on the female connectors.
Plug the connectors to the COM and NO positions of the Defrost
Relay.
Defrost (Heater) Relay Using the KE2 Wire Harness
The orange wires are used for the heater control.
Locate the orange with black stripe, and black with orange stripe.
Plug the black with orange stripe to the COM terminal.
Plug the orange w. black stripe to the NO position of Defrost Relay.
Confirm combined heater load is not over 30 amps.
9
10
Liquid Line Solenoid /Compressor Relay
Strip the end of the 2 wires used for the liquid line solenoid.
Locate 2 90° female spade connectors in the accessories kit.
Crimp on the female connectors.
Plug the connectors to the COM and NO positions of the Liquid
Line Solenoid /Compressor Relay
Liquid Line Solenoid (LLS)/Comp. Relay Using KE2 Wire Harness
The yellow wires are used for Liquid Line Solenoid control.
Locate a 3-position connector from the accessories kit.
Fasten the black with yellow stripe to the fused lead.
Fasten yellow w. black stripe from the LLS to NO terminal position.
Plug into the location as indicated in Wiring Schematic.
Confirm compressor load is not over 30 FLA.
Fan Relay
Strip the end of the 2 wires used for fan control.
Locate 2 90° female spade connectors in the accessories kit.
Crimp on the female spade connectors.
Plug the connectors to the COM and NO positions of the Fan Relay.
Fan Relay Using the KE2 Wire Harness
The blue wires are used for fan control.
They are blue with a black stripe, and the black with a blue stripe.
Plug the black with a blue stripe to the COM terminal.
Plug the blue with a black stripe to the NO position of the Fan
Relay
Confirm combined fan motor load is not over 30 FLA.