Q.1.35 January 2016
Page 8
© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Existing wiring.
Start by removing all of the exist-
ing wires from the terminal strip.
Determine the location of the fol-
lowing: incoming power, fan leads,
heater leads, defrost termination
leads, and fan delay leads.
14
Evaporator wiring – Controller
Strip the end of the wires used to
power the controller.
Attach to the line power to provide
continuous power to the controller.
15
Evaporator wiring – Fans
Strip the ends of the wires (con-
nected to the KE2 Adaptive
Control) used to control the evapo-
rator fans.
The fan wires from the controller
can be attached to the terminal
block using either screw down ter-
minals or spade connectors.
Attach the black wire with blue
stripes to the L1/Line. This wire
will be connected to COM of fan
relay on the controller.
Attach blue wire with black
stripes to the NO terminal on
the Fan Relay to one set of the fan
leads. This wire will be connected
to the NO of the fan relay on the
controller.
Connect L2/Neutral to remaining
fan leads.
16
15
16
KE2 Adaptive
Control
Quick Start Guide