dLOc
Defrost Lockout
Variable
In variables menu, display when1st or 2nd Auxiliary input (AU1 or AU2)set to Defrost Lockout (dFLO) and is active
dOOr
Door Open Alarm
Alarm
If door is open and room temperature is 5 degrees above temperature setpoint (tS) + temperature differential (diF) and input
stays active for 90 minutes, ignores temperature alarm delay (tAd)
Door Input
Setpoint
Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2) - is used to determine if the door is open or closed
dPd
Defrost Per Day
Setpoint
Number of defrosts per day 0-12, Custom (CUS)
dPTR
Defrost parameter
Setpoint
If Defrost Initiation mode (dFit)
= Demand Defrost (dEnd); Coefficient to KE2 Defrost algorithm
drAn
Drain
System State
Displays when system is in drain mode
drCL
Door Closed
Variable
In Variables menu, display when AU1 and AU2 set to dOOr and is inactive
drOn
Door Open
Variable
In Variables menu, display when AU1 and AU2 set to dOOr and is active
drnt
Drain Time
Setpoint
Amount of time in drain mode
dtSP
Defrost Term Temperature Setpoint
Setpoint
Coil temperature reaches defrost term temperature setpoint to terminate defrost
dttA
Defrost Termination on Time
Alarm
Defrost terminated on time instead of temperature for two consecutive cycles
dtyP
Type of Defrost
Setpoint
Air or Electric
ECdF
Excessive Defrost
Alarm
Controller has performed 11 consecutive defrost cycles without terminating on temperature
EdiF
Extreme Differential
Setpoint
ADVANCED TOPIC: Contact KE2 Therm for assistance
ELEC
Electric
Setpoint
Defrost option
FAH
Fahrenheit
Setpoint
Default for all temperatures displayed
FdSP
Fan delay temp Setpoint
Setpoint
Coil temp must reach this setpoint to turn fans back on after defrost
FndF
Fan State During Defrost
Setpoint
Fans on or off during defrost
FndL
Fan Delay
System State
Displays when system is in fan delay mode
Fndt
Max fan delay time
Setpoint
Maximum time system can stay in fan delay (FndL) mode
FnrL
Fan Relay
Variable
Status of whether fan relay is energized or de-energized
FrEF
Fan mode during refrigeration
Setpoint
Determines how fan operates during refrigeration mode -- permanent (PErn), On with compressor (OnCp) Title 24 (ti24)
FSCH
Forced schedule
Setpoint
Controller automatically changed from demand defrost to schedule defrost due to excessive defrost alarm
HEtr
Heater mode
Setpoint
If defrost mode = ELEC: whether to leave the defrost relay energzied during defrost cycle or to utilze advanced heater mgmnt.
HtA
High Temperature Alarm
Alarm
Average temperature is above the Temperature Setpoint (tS) + Temperature Differential Setpoint diF + High Alarm Offset
(HAO) for the amount of time in the Temperature Alarm Delay (tAd)
HAO
High Alarm Offset
Setpoint
Number of degrees above the Temperature Setpoint (tS) for a High Temp Alarm (HtA) condition.
inid
Inititate Defrost
Variable
Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2) - digital input that will initiate defrost
LAO
Low Alarm Offset
Setpoint
Number of degrees below the Temperature Setpoint (tS) for a Adaptive Control Alarm (LtA) condition.
LtA
Low Temperature Alarm
Alarm
Average temperature is below the Temperature Setpoint (tS) - Low Alarm Offset (LAO) for the amount of time in the Tempera-
ture Alarm Delay (tAd)
NOAL
No Alarm
Alarm
System is clear of alarms
OFF
System Off
System State
The system is currently not running
OFFt
Minimum Compressor Off Time
Setpoint
Minimum time the liquid line solenoid/compressor relay must remain off before it can be energized again
OnCP
On with compressor
Setpoint
Fans are on when compressor is running
OPEn
Open
Setpoint
Digital input is active/inactive when open
Pdt
Defrost pump down time
Setpoint
Amount of time to pump down the system before defrost
PErn
Permanent
Setpoint
Fans on permanently
PF
Power Failure alarm
Alarm
Alarm indicates that there was an interruption in the power supply to the controller
rEFr
Refrigerate Mode
System State
System mode displayed when controller is in cooling mode
rt1
Room Temperature 1
Variable
Room temperature displayed if AU1 (1st Auxiliary input) is set to rtP (Room Temp)
rt2
Room Temperature 2
Variable
Room temperature displayed if AU2 (2nd Auxiliary input) is set to rtP (Room Temp)
rtP
Room Temp
Variable
Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2) - input is used as an additional room temperature averaged in
with the other room temperature inputs
rUnt
Minimum Compressor Run Time
Setpoint
Minimum amount of time the liquid line solenoid/compressor relay must remain on after it is energized
ScHd
Schedule Defrost
Setpoint
Choice for Defrost Initiation Mode (dFit)
SHrt
Short
Setpoint
Digital input is active/inactive when short
StA1
State of 1st Auxiliary Input
Setpoint
Digital input active state for 1st Auxiliary input (AU1) - set whether it is open or short
StA2
State of 2nd Auxiliary Input
Setpoint
Digital input active state for 2nd Auxiliary input (AU2) - set whether it is open or short
SYOF
System Off
Variable
Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2)- digital input that puts the controller into System Off Mode
SYOn
System On
Variable
Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2)- digital input that puts the controller into System On Mode
SYSt
System State
Variable
Displays mode of system operation
t2nd
2nd Room Temp Setpoint
Setpoint
Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2) - input is used to switch between the main Room Temp
Setpoint and the 2nd Room Temp Setpoint
t2Of
2nd Air Off
Variable
Use main air temperature setpoint
t2On
2nd Air On
Variable
Use second air temperature
tAd
Temp Alarm Delay
Setpoint
Amount of time to delay a high temp or low temp alarm
tErd
Terminate Defrost
Variable
In Variables menu, display when 1st or 2nd Auxiliary input (AU1 or AU2) set to trdF (terminate defrost) and is active
ti24
Title 24
Setpoint
Configure the controller to be Title 24 for runtime compliant during refrigeration system’s off cycle
tOd
Time of day
Setpoint
Time is displayed based on 24 hour clock
tP1
Monitor Temperature 1
Variable
When AU1 is set to tP1 controller is monitoring temperature only
tP2
Monitor Temperature 2
Variable
When AU2 is set to tP1 controller is monitoring temperature only
trdF
Terminate Defrost
Setpoint
Choice for input type for1st or 2nd Auxiliary input (AU1 or AU2) - digital input that will terminate defrost
tS
Temperature Setpoint
Setpoint
Room temperature to be maintained
tS2
Temperature Setpoint 2
Setpoint
Alternate room temperature setpoint
Unt
Temp units
Setpoint
Fahrenheit (FAH) or Celsius (CEL)