dLOc

Defrost Lockout

Variable

In variables menu, display when1st or 2nd Auxiliary input (AU1 or AU2)set to Defrost Lockout (dFLO)  and is active

dOOr

Door Open Alarm

Alarm

If door is open and room temperature is 5 degrees above temperature setpoint (tS) + temperature differential (diF) and input 

stays active for 90 minutes, ignores temperature alarm delay (tAd)

Door Input

Setpoint

Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2) - is used to determine if the door is open or closed

dPd 

Defrost Per Day 

Setpoint

Number of defrosts per day 0-12, Custom (CUS)

dPTR

Defrost parameter

Setpoint

If Defrost Initiation mode (dFit)

 

= Demand Defrost (dEnd); Coefficient to KE2 Defrost algorithm

drAn

Drain

System State

Displays when system is in drain mode

drCL

Door  Closed

Variable

In Variables menu, display when AU1 and AU2 set to dOOr and is inactive

drOn

Door Open

Variable

In Variables menu, display when AU1 and AU2 set to dOOr and is active

drnt

Drain Time

Setpoint

Amount of time in drain mode

dtSP

Defrost Term Temperature Setpoint

Setpoint

Coil temperature reaches defrost term temperature setpoint to terminate defrost

dttA

Defrost Termination on Time

Alarm

Defrost terminated on time instead of temperature for two consecutive cycles

dtyP

Type of Defrost  

Setpoint

Air or Electric

ECdF

Excessive Defrost

Alarm

Controller has performed 11 consecutive defrost cycles without terminating on temperature

EdiF

Extreme Differential

Setpoint

ADVANCED TOPIC: Contact KE2 Therm for assistance

ELEC

Electric

Setpoint

Defrost option

FAH

Fahrenheit

Setpoint

Default for all temperatures displayed

FdSP

Fan delay temp Setpoint

Setpoint

Coil temp must reach this setpoint to turn fans back on after defrost

FndF

Fan State During Defrost

Setpoint

Fans on or off during defrost

FndL

Fan Delay

System State

Displays when system is in fan delay mode 

Fndt

Max fan delay time

Setpoint

Maximum time system can stay in fan delay (FndL) mode

FnrL

Fan Relay

Variable

Status of whether fan relay is energized or de-energized

FrEF

Fan mode during refrigeration

Setpoint

Determines how fan operates during  refrigeration mode -- permanent (PErn), On with compressor (OnCp) Title 24 (ti24)

FSCH

Forced schedule

Setpoint

Controller automatically changed from demand defrost to schedule defrost due to excessive defrost alarm

HEtr

Heater mode

Setpoint

If defrost mode = ELEC: whether to leave the defrost relay energzied during defrost cycle or to utilze advanced heater mgmnt.

HtA

High Temperature Alarm

Alarm

Average temperature is above the Temperature Setpoint (tS) + Temperature Differential Setpoint diF + High Alarm Offset 

(HAO) for the amount of time in the Temperature Alarm Delay (tAd)

HAO 

High Alarm Offset

Setpoint

Number of degrees above the Temperature Setpoint (tS) for a High Temp Alarm (HtA) condition.

inid

Inititate Defrost

Variable

Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2) - digital input that will initiate defrost

LAO 

Low Alarm Offset

Setpoint

Number of degrees below the Temperature Setpoint (tS) for a Adaptive Control Alarm (LtA) condition.

LtA

Low Temperature Alarm

Alarm

Average temperature is below  the Temperature Setpoint (tS) - Low Alarm Offset (LAO) for the amount of time in the Tempera-

ture Alarm Delay (tAd)

NOAL

No Alarm

Alarm

System is clear of alarms

OFF

System Off

System State

The system is currently not running

OFFt

Minimum Compressor Off Time

Setpoint

Minimum time the liquid line solenoid/compressor relay must remain off before it can be energized  again

OnCP

On with compressor

Setpoint

Fans are on when compressor is running

OPEn

Open

Setpoint

Digital input is active/inactive when open

Pdt

Defrost pump down time

Setpoint

Amount of time to pump down the system before defrost

PErn

Permanent

Setpoint

Fans on permanently

PF

Power Failure alarm

Alarm

Alarm indicates that there was an interruption in the power supply to the controller

rEFr

Refrigerate Mode

System State

System mode displayed when controller is in cooling mode

rt1

Room Temperature 1

Variable

Room temperature displayed if AU1 (1st Auxiliary input) is set to rtP (Room Temp)

rt2

Room Temperature 2

Variable

Room temperature displayed if AU2 (2nd Auxiliary input) is set to rtP (Room Temp)

rtP 

Room Temp

Variable

Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2)  - input is used as an additional room temperature averaged in 

with the other room temperature inputs

rUnt

Minimum Compressor Run Time

Setpoint

Minimum amount of time the liquid line solenoid/compressor relay must remain on after it is energized

ScHd

Schedule Defrost

Setpoint

Choice for Defrost Initiation Mode (dFit)

SHrt

Short

Setpoint

Digital input is active/inactive when short

StA1

State of 1st Auxiliary Input

Setpoint

Digital input active state for 1st Auxiliary input (AU1) - set whether it is open or short

StA2

State of 2nd Auxiliary Input

Setpoint

Digital input active state for 2nd Auxiliary input (AU2) - set whether it is open or short

SYOF

System Off

Variable

Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2)- digital input that puts the controller into System Off Mode

SYOn

System On

Variable

Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2)- digital input that puts the controller into System On Mode

SYSt

System State

Variable

Displays mode of system operation

t2nd

2nd Room Temp Setpoint

Setpoint

Choice for input type for 1st or 2nd Auxiliary input (AU1 or AU2) - input is used to switch between the main Room Temp 

Setpoint and the 2nd Room Temp Setpoint 

t2Of

2nd Air Off

Variable

Use main air temperature setpoint

t2On

2nd Air On

Variable

Use second air temperature 

tAd 

Temp Alarm Delay

Setpoint

Amount of time to delay a high temp or low temp alarm

tErd

Terminate Defrost

Variable

In Variables menu, display when 1st or 2nd Auxiliary input (AU1 or AU2) set to trdF (terminate defrost) and is active

ti24

Title 24

Setpoint

Configure the controller to be Title 24 for runtime compliant during refrigeration system’s off cycle

tOd

Time of day

Setpoint

Time is displayed based on 24 hour clock

tP1

Monitor Temperature 1

Variable

When AU1 is set to  tP1 controller is monitoring temperature only

 

tP2

Monitor Temperature 2 

Variable

When AU2 is set to  tP1 controller is monitoring temperature only

trdF

Terminate Defrost

Setpoint

Choice for input type for1st or 2nd Auxiliary input (AU1 or AU2) - digital input that will terminate defrost

tS

Temperature Setpoint

Setpoint

Room temperature to be maintained

tS2

Temperature Setpoint 2

Setpoint

Alternate room temperature setpoint

Unt

Temp units

Setpoint

Fahrenheit (FAH) or Celsius (CEL)

KE2 Adaptive

Control

Quick Start Guide

Summary of Contents for AdaptiveControl

Page 1: ...rovided Conduit to go between the controller and the evaporator 2 Conduit connectors straight or elbow as required 8 High voltage wires matched to the load of the heaters fans liquid line solenoid and...

Page 2: ...Vapor Mix Restrictor TEV or EEV Warm Liquid ColdVapor HotVapor Warm Air Cold Air Evaporator Compressor Condenser SaturationTemp F from receiver pressure LiquidTemp atValve F Subcooling Suction Pressu...

Page 3: ...lect two places that are the last to defrost preferably at each end of the evaporator More often than not on coils the location of the sensor is a short distance from the end approximately 1 to 1 1 2...

Page 4: ...e Control Cutalengthofconduittogofromthecontrollertotheevaporator Measure the distance between the controller and evaporator to account for the extra length necessary to properly route conduit Determi...

Page 5: ...end of the conduit to the controller 5 5 115V 208 240V Wiring the controller Locate the Voltage Selector Switch It is a 2 position switch with red indicator The selected voltage will be displayed on...

Page 6: ...lug the connectors to the COM and NO positions of the Liquid Line Solenoid Compressor Relay Liquid Line Solenoid LLS Comp Relay Using KE2 Wire Harness The yellow wires are used for Liquid Line Solenoi...

Page 7: ...he controller to the plastic posts Connecting sensor wires to controller The temperature sensors are designed to be attached to the con troller using 2 position screw terminals The terminals are locat...

Page 8: ...controller 15 Evaporator wiring Fans Strip the ends of the wires con nected to the KE2 Adaptive Control used to control the evapo rator fans The fan wires from the controller can be attached to the te...

Page 9: ...ect L2 Neutral to the remain ing defrost leads The defrost safety should not be re moved from the circuit Its purpose is to prevent the heaters from over heating and causing damage 18 Copyright 2016 K...

Page 10: ...ary 2016 Page 10 Copyright 2016 KE2 Therm Solutions Inc Washington Missouri 63090 Figure 8 Wiring Schematic Ladder Diagram Figure 8 Wiring Schematic Using KE2Terminal Board KE2 AdaptiveControl Quick S...

Page 11: ...ew included The end with multiple loops is designed to hold the sensor Locate the best place to install the sensor The sensor should be located between 6 and 12 inches away from the face of the evapor...

Page 12: ...erference being introduced into the sensor wires Interference can be introduced when sensor wires are located near high voltage lines High voltage is defined by Underwriter s Laboratories as above 30V...

Page 13: ...venient loca tion where it can be easily located for future service 27 Setting the dip switch to activate on board buzzer To disable the audible alarm buzzer feature of the KE2 Adaptive Control the di...

Page 14: ...d dFt diF OFFt Runt FrEF AU1 StA1 AU2 StA2 tS2 tOd d1 d2 d3 d4 d5 d6 d7 d8 d9 d10 d11 d12 dtSP drnt fdSP Fndt FndF Pdt HAO LAO tAd Adr Unt CLAL Schedule Defrost w Custom Defrost Per Day tS dtyP dFit d...

Page 15: ...0V 208 240V StorageTemp 40 to 120 F 40 to 49 C OperatingTemp 40 to 120 F 40 to 49 C Display 4 digit 7 segment LED IP Rating IP65 Inputs 4 3 colored 15 temp sensors KE2 SKU 21151 2 dual purpose tempera...

Page 16: ...ive cycles ECdF Excessive Defrost Controller has performed 11 consecutive defrost cycles without terminating on temperature PF Power Failure Indicates power has been off and just turned on only when d...

Page 17: ...00 diS 23 59 diS d2 Start time of Defrost 2 0 00 diS 23 59 diS d3 Start time of Defrost 3 0 00 diS 23 59 diS d4 Start time of Defrost 4 0 00 diS 23 59 diS d5 Start time of Defrost 5 0 00 diS 23 59 diS...

Page 18: ...lock d12 Defrost 12 Setpoint Start time of Defrost 12 when in defrosts per day dPd is custom CUSt based on 24 hour clock dAUt Defrost Auto Variable Defrost is in Automatic mode i e normal operation dE...

Page 19: ...arm Offset LAO for the amount of time in theTempera ture Alarm Delay tAd NOAL No Alarm Alarm System is clear of alarms OFF System Off System State The system is currently not running OFFt Minimum Comp...

Page 20: ...ay then press Use the up arrow and down ar row to set the time STEP 7 Press the button to save settings and return to the main screen room temp will be displayed Custom Defrost Setup The following ste...

Reviews: