V7.00
24905_EDEBD
A0272-5019-1_EN
77
Under the item Auto configuration mode, you can start automatic monitoring of the
connected capacitor stages under the menu item
Extra
,
Commissioning
,
Stages
,
Auto configuration mode
,
Start.
First, the configured parameters are displayed.
If needed, these can be corrected here or, if they are already correct, confirmed with
N
(
OK
). After the last confirmation, all capacitor stages are switched off, and the auto
configuration mode can be started. During the procedure, the stages are switched on
individually, and the stage power is determined. This can be interrupted by pressing
(
Stop
) at any time. The progress is illustrated in the status display. Along with this,
the connected capacitor stages are hooked up, one after the other. From the current
consumption measured, the
multicomp D6-xxx-7
determines the corresponding stage
power. After successfully determining the stage power, the result is displayed and can be
saved by confirming it (press button
(
Return
) repeatedly, until the prompt
Save
parameters Yes/No
appears). If measurement errors have occurred, they can be discard-
ed, and the mode be restarted.
A prerequisite for performing the auto configuration mode is, however:
1. Measurement via induced current transformer and current measuring module
multisio
D2/4CI
or energy measuring module
multimess D4
2. Correct programming of the primary and secondary voltage
3. Correct programming of the primary and secondary current of the induced current
transformer
4. Correct programming of the primary and secondary voltage of the energy measuring
module
5. Possible additionally connected modules must be detected and stored with the help of
the Settings
,
Module / Display
,
Module management menu item
6. The capacitive or inductive stages must be connected
If all these prerequisites are met, the auto configuration mode of the stage powers can be
started.
Under the item
Stage parameters direct input
, all stage parameters can also be entered
manually.
The following parameters are available:
1. Stage power from 0.00 to 999.9 kvar
2. Capacitive or inductive stages
System operation
System operation