V7.00
24905_EDEBD
A0272-5019-1_EN
21
Commissioning
Continued
Harmonics monitoring
Active, THD 8%,
error message is displayed
Induced current measurement
Disabled
Password
9999/all functions can be accessed
Limit overvoltage switch-off
Active, 253 V Ph-N, stages switch off, error
message is displayed
Analog controlled compensation stage
off
+limit induced current exceeded
150%
Type
positive
Output
Alarm relay and excess current switch off
Limit induced current exceeded
00%
Type
off
Output
off
Switch mode
toff -
d
- ton
Stage change after 24 hrs.
No
Unaffected by a RESET:
Bus address
Date and time
Language