5.3
Setting range of the configurable parameters:
primary voltage
1 V to 9999 kV Ph-Ph
Secondary voltage
100 V to 500 V Ph-Ph
Primary current
1 A to 99.99 kA
Secondary current
1 and 5 A
Rot.field U
L1N, L2N, L3N, L12, L23, L31
Rot.field I
L1, L2, L3, -L1, -L2, -L3
Consumption target cosφ
ind. 0.80 to cap. 0.80
Recovery target cosφ
ind. 0.80 to cap. 0.80
FTS alarm cosφ
ind. 0.50 to cap. 0.50
Attenuation coefficient for current
0 to 6
Attenuation coefficient for voltage
0 to 6
Attenuation coefficient Q
miss
0 to 6
Idle time
0 to 300 sec.
Alarm relay time
0 to 3000 sec.
Hysteresis connection
70 to 150%
Hysteresis switch-off
70 to 150%
Switching interval
0 to 480 sec.
Operating cycle limit
0 to 99990
Cabinet No.
1 to 6
Stage power
0 to 999.9 kvar inductive or capacitive
Discharge time
0 to 900 sec.
Detuning
0, 5.5, 7, 8, 12.5, 14%
Stage switching mode
Automatic, manual off, manual on
Harmonics monitoring
0 to 99%, deactivatable
Overvoltage switch-off
Dependent on primary voltage
Excess current switch-off
110% to 200%
Undercurrent switch-off
0 to 90%
Limit THD
0 to 10%
Switching threshold fan
0 to 70°C / hysteresis = 0°C to 25°C
Operating point alarm
0 to 70°C / hysteresis = 0°C to 25°C
Operating point overtemperature
0 to 70°C / hysteresis = 0°C to 25°C
Scanning frequency
Automatic, fixed 50 Hz, fixed 60 Hz
Password
No password (9999, meaning all functions
are accessible)
Language display
German, English, French
Contrast setting
60% to 100%
System operation