Under the item “Error state messages,” messages are shown that must be
deleted manually. This means that these messages, which are relevant for the correct
operation of the system, do not go unnoticed.
The following status and error messages can be displayed:
Status messages
(must be acknowledged)
E01
Power failure has occurred
E02
A limit has been violated
E05
Reset has been performed
E09
Operating cycles of a stage above limit (contactor stage)
E10
Limit violation of voltage
E11
Current direction
(k and I of the current transformer were swapped)
E12
Facility too small (FTS)
E13
RTC capacitor empty
E14
Parameter error
(default value replaces incorrect value)
E15
Input overload
(current or voltage at the basic module)
Error messages
(do not have to be acknowledged)
E17
No measuring voltage
Alarm relay
Stage switch-off
E19
Stage power?
Alarm relay
E20
Facility too small (FTS)
Alarm relay
E21
Limit violated
Alarm relay
E22
Limit violated,
stage switch-off active
Alarm relay
Stage switch-off
E23
Stage switch-off temperature reached on at least one
temperature sensor (stage switch-off always active)
Alarm relay
E24
Alarm temperature exceeded or short circuit on any
temperature probe, or broken wire
Alarm relay
E25
No measuring current (for low load operation, the stag-
es are switched off after one hour)
Alarm relay
System operation