V7.00
24905_EDEBD
A0272-5019-1_EN
146
10.3
Function of the DIP switches
10.3.1
Operating mode
For every input, the multisio D2-4DI differentiates
between the operating modes “normal” and “manual.” Switching
is performed via the DIP switches 5 to 8. The DIP switches
are assigned to the outputs as follows:
• DIP switch 5 switches the operating mode of input 1
• DIP switch 6 switches the operating mode of input 2
• DIP switch 7 switches the operating mode of input 3
• DIP switch 8 switches the operating mode of input 4
If the DIP switch is set to Off, the respective input
is in normal operating mode. If the
DIP switch is set to On, the respective
input is in manual operating mode.
Illustrated switch setting:
OFF = white
ON = gray
Normal operating mode
In normal operating mode, the current state of the associated input is further processed.
Manual operating mode
In manual operating mode, the state of DIP switches 1 to 4 is further processed, instead
of the state of the corresponding input. The DIP switches are assigned to the inputs as
follows:
• DIP switch 1 switches the state of input 1
• DIP switch 2 switches the state of input 2
• DIP switch 3 switches the state of input 3
• DIP switch 4 switches the state of input 4
If the DIP switch is set to Off, the input state passive/off is further processed. If the DIP
switch is set to On, the input state active/on is further processed.
Appendix – multisio D2-4DI digital input module