Commissioning
3
Commissioning guideline
for the multicomp D6-xxx-7
This guideline helps you to correctly start up the compensation controller
multicomp D6-xxx-7
. It provides you with step by step instructions to help you find
the options relevant for you in the operating instructions.
To begin with, there are two cases in which the commissioning procedure for the
multicomp D6-xxx-7
differs.
Case 1:
You have bought a complete compensation unit from
KBR
, and the controller
is already installed. If this is the case, certain settings are already preconfigured in the
controller.
Case 2:
You only bought the controller, or the controller with additional modules
(
multisio D2-1T2RO, multisio D2-4RO, multisio D4-4RO ISO, multisio D2-4CI
and
multimess D4
) and individual capacitor stages, but the device is not assembled. In this
case, the controller is delivered with the default settings (refer to chapter Default settings)
and has thus not been preconfigured.
IMPORTANT SAFETY INFORMATION
CAUTION
The discharge times are automatically predefined for the following programmed stage
powers. However, these must be checked and corrected if they differ from the capacitor
specifications.
Capacitor power
Discharge resistance
Discharge time
2.5 kvar – 7.5 kvar
300 kOhm
60 seconds
10 kvar–17.5 kvar
300 kOhm
120 seconds
20 kvar and above
300 kOhm
180 seconds