8.5.8
Standards and miscellaneous
Ambient
conditions
Standards
and subsequent
amendments
DIN EN 60721-3-3/A2: 1997; 3K5+3Z11;
(IEC721-3-3; 3K5+3Z11)
Operating temperature
-5°C … +55°C
Air humidity
5% … 95% non-condensing
Storage temperature
-25°C … +70°C
Electrical
safety
Standards
and subsequent
amendments
DIN EN 61010: 2001 +B1: 2002; +B2:
2004
Protection category
II
Overvoltage
category
CAT III: U
PH-PH
up to 400V
Protection type
IP 20
DIN EN 60529:1991 +A1:2000
Electromagnetic
compatibility
DIN EN 61000-6-1: 2007,
DIN EN 61000-6-2: 2005,
DIN EN 61000-6-3: 2007,
DIN EN 61000-6-4: 2007
8.5.9
Commissioning the multimess D4 at the multicomp D6-xxx-7
To commission the multimess D4 at the multicomp D6-xxx-7, please proceed as follows:
1. Connect the measuring module to the multicomp D6-xxx-7
via the module bus interface.
2. At the terminals 10 (L1), 11 (L2), 12 (L3) and 13 (N), connect the
measuring voltage (the operating voltage of the measuring module).
3. On the multicomp display, select the menu Settings
> Extras > Settings > Modules > Module management > Module.
4. Displayed are the multicomp basic module,
modules already existing and the menu item “scan.”
5. After selecting this menu item with the cursor buttons,
the scan mode can be started with the scan button. The scan display will flash.
This way, the scan button on the measuring module (close to
the status LED, flashing green) is unlocked.
multisio D2 4CI module multimess D4- Appendix