Part 2 - Out
door Unit Engineering Da
ta
Amazon Unitario Top Discharge
17
16-22HP
Table 2-1.2: 16-22HP specifications
HP
16
18
20
22
Model name
K2UF-450 DN4S
K2UF-500 DN4S
K2UF-560 DN4S
K2UF-615 DN4S
Power supply
V/Ph/Hz
380-415/3/50
Cooling
1
Capacity
kW
45.0
50.0
56.0
59.0
Power input
kW
20.96
28.09
34.22
35.41
EER
2.15
1.78
1.64
1.67
Heating
2
(rated)
Capacity
kW
45.0
50.0
56.0
59.0
Power input
kW
13.78
14.92
15.98
19.57
COP
3.27
3.27
3.35
3.50
3.01
Heating
2
(max)
Capacity
kW
50.0
56.0
63.0
66.2
Power input
kW
16.58
18.02
19.21
23.22
COP
3.02
3.11
3.28
2.85
SEER
5.58
5.43
5.38
5.07
ηs,c
%
220.3
214.2
212.2
199.9
SCOP
4.06
3.95
4.31
4.42
ηs,h
%
159.4
155.0
169.5
173.7
Connected
indoor unit
Total capacity
50-150% of outdoor unit capacity
Maximum quantity
26
29
33
36
Compressor
Type
DC inverter
Quantity
1
2
Oil type
FAmazon Unitario Top Discharge8H
Start-up method
Soft start
Fan
Type
Propeller
Motor type
DC
Quantity
1
2
Motor output
kW
0.92
0.92
0.56×2
0.56×2
Airflow rate
m
3
/h
13000
13000
17000
17000
Drive type
Direct
Refrigerant
Type
R410A
Factory charge
kg
13
13
17
17
Pipe
connections
3
Liquid pipe
mm
Φ15.9
Φ19.1
Gas pipe
mm
Φ31.8
Φ31.8
Sound pressure level
4
dB(A)
65
66
Sound power level
dB(A)
86
91
89
89
Net dimensions (W×H×D)
mm
1340×1635×850
1340×1635×825
Packed dimensions (W×H×D)
mm
1405×1805×910
Net weight
kg
277
295
344
344
Gross weight
kg
304
322
364
364
Ambient temp.
operation range
Cooling
o
C
-5 ~ 48
Heating
o
C
-23 ~ 24
Notes:
1.
Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.
Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Diameters given are those of the unit’s stop valve.
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.