Part 3 - S
yst
em Design and Ins
talla
tion
Amazon Unitario Top Discharge
159
… box continued from previous page
Piping orientation during brazing
Brazing should be conducted downwards or horizontally to avoid filler leakage.
Figure 3-5.6: Piping orientation during brazing
A
D
Piping overlap during brazing
Table 3-5.3 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints
on piping of different diameters. Refer also to Figure 3-5.7.’
Figure 3-5.7: Piping overlap and gap for brazed joints
A
D
B
Legend
A
Inner diameter of larger pipe
D
Outer diameter of smaller pipe
B
Inlaid depth (overlap)
Table 3-5.3: Piping overlap and gap for brazed joints
1
D (mm)
Minimum
permissible B (mm)
Permissible A – D
(mm)
5 < D < 8
6
0.05 - 0.21
8 < D < 12
7
12 < D < 16
8
0.05 - 0.27
16 < D < 25
10
25 < D < 35
12
0.05 - 0.35
35 < D < 45
14
Notes:
1. A, B, D refer to the dimensions shown in Figure 3-5.7.
Filler
Use a copper/phosphorus brazing alloy (BCuP) filler that does not require flux.
Do not use flux. Flux can cause corrosion of piping and can affect the performance of compressor oil.
Do not use anti-oxidants when brazing. Residue can clog piping and damage components.
Brazing
Brazing
Brazing
Brazing