Ka
ysun Amaz
on Unit
ario T
op Dischar
ge Engineering Da
ta Book
Amazon Unitario Top Discharge
12
Table 1-5.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units
Outdoor unit capacity
Sum of capacity indexes of
connected indoor units (standard
indoor units only)
Maximum number of
connected indoor units
kW
HP
Capacity
index
50.0
18
500
250 to 750
29
56.0
20
560
280 to 840
33
59.0
22
590
295 to 885
36
67.0
24
670
335 to 1005
39
73.0
26
730
365 to 1095
43
75.5
28
755
377.5 to 1132.5
46
85.0
30
850
425 to 1275
50
90.0
32
900
450 to 1350
53
The number of connected indoor units is 8 and the maximum number of connected indoor units on the 20HP outdoor
unit is 33, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor unit:
a) The sum of the indoor unit CIs is 706 and the CI of the 20HP outdoor unit (K2UF-560 DN4S-E) is 560, so the
combination ratio is 706 / 560 = 126%.
b) Using the outdoor unit’s cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.6 and 1-5.7.
Table 1-5.6: Extract from Table 2-8.7 K2UF-560 DN4S-E cool
-
ing capacity
Table 1-5.7: Cooling capacity calculated by interpolation
CR
Outdoor air
temp.
(°C DB)
Indoor air temp.
(°C DB / °C WB)
CR
Outdoor air
temp.
(°C DB)
Indoor air temp.
(°C DB / °C WB)
25.8 / 18.0
25.8 / 18.0
TC
PI
TC
PI
kW
kW
kW
kW
130%
31
61.3
14.33
130%
33
60.4
14.88
33
60.4
14.88
35
59.5
15.46
B = 60
1
120%
31
60.2
13.88
120%
33
59.3
14.44
33
59.3
14.44
35
58.4
15.00
Notes:
1.
59.3 + (60.4 – 59.3) × (126 – 120) / (130 – 120) = 60
.