CLASSIC 800 Product Manual
Setup & Operation
Figure 23 - Setting the 0% & 100% Thermal Signal
Thermal Signal
100%
0
Relay 1
Relay 2
Fault
Set Point 1
Set Point 2
Run Mode
Bypass
RUN
SET
1
2
CLASSIC
™
Thermal Signal
100%
0
Relay 1
Relay 2
Fault
Set Point 1
Set Point 2
Run Mode
Bypass
RUN
SET
1
2
CLASSIC
™
Set Point 1 is flashing
for the LED-0 Pointer
Set Point 2 is flashing
for the LED-100 Pointer
Single LED
displays Pointer
Single LED
displays Pointer
Increase Set Point
Increase Set Point
Decrease Set Point
Decrease Set Point
9. View or Adjust the 0% & 100% Thermal Signal LEDs:
1.
Press and release
SET
until the
Set Point 1
(LED-0) or
Set Point 2
(LED-100) status LED is
flashing
and
the
Run Mode
LED is off.
2.
The
Thermal Signal Bar Graph
now shows the setting of the LED Pointer.
3.
To adjust the LED Pointer, press and release the
Left
or
Right Arrow
keys.
4.
When satisfied with your configuration, press and release
SET
to continue to the next Programmable
Variable OR press and release
RUN
to return to
Run Mode.