Ventilation requirements for simultaneous operation with other fireplaces.
Oxygen or air is permanently required for the combustion process. As a rule, the air present in the installation room
is sufficient. In case of well-sealed windows and doors, presence of mechanical vents (e.g. kitchen or bathroom) or
other fireplaces (also gas boiler) in the dwelling, the proper air supply can be sensitively disturbed. If this is the case,
it is possible to supply the combustion air directly from the outside or from another sufficiently ventilated room
(e.g. cellar). For this purpose, the Bank, Hang, Stand, Tower, Tube and Wave stoves have a combustion air spigot on
the back of the appliance with an outer diameter of 100 mm. This can be connected at the bottom or at the back,
depending on the model. The external air connection of the LuTo VIII Tower has an external diameter of 120 mm and
is located in the base at the back of the stove.
Combustion air connection
Combustion air connec-
tion for „Hang“ & „Stand“
Combustion air
connection
back
bottom
For this purpose, the Kanuk Design LuTo XV and LuTo VIII have a combustion air spigot on the back of the unit mea-
suring 202 mm x 40 mm.
Combustion air
spigot
Chimney
Multiple use of the chimney is permissible in closed mode (the Kanuk Design LuTo is already equipped with a self-
closing door in the basic version). The fire-technical dimensioning is carried out according to DIN 13384 parts 1, 2
and 3 with the value triple specified in table 1.
note:
We can only guarantee the operational safety and nominal heat output of the Kanuk® Design stoves if the
adequate fire-technical dimensioning of the chimney has been proven by a calculation according to DIN 13384
Parts 1, 2 and 3 and has been certified by a district chimney sweep.
Summary of Contents for Bank
Page 1: ...BEDIENUNGSANLEITUNG MODE D EMPLOI INSTRUCTION MANUAL...
Page 4: ......
Page 5: ...BEDIENUNGSANLEITUNG Dieses Produkt eignet sich nicht als Hauptheizger t...
Page 24: ......
Page 25: ...BEDIENUNGSANLEITUNG Dieses Produkt eignet sich nicht als Hauptheizger t...
Page 51: ...Kanuk GmbH Hauptstra e 131 01744 Dippoldiswalde 51 DE Kanuk Design Eco Design...
Page 54: ......
Page 55: ...MODE D EMPLOI Ce produit ne convient pas comme appareil de chauffage principal...
Page 74: ......
Page 75: ...MODE D EMPLOI Ce produit ne convient pas comme appareil de chauffage principal...
Page 101: ...Kanuk GmbH Hauptstra e 131 01744 Dippoldiswalde 101 FR Kanuk Design Eco Design...
Page 104: ......
Page 105: ...INSTRUCTION MANUAL This product is not suitable as a main heater...
Page 124: ......
Page 125: ...INSTRUCTION MANUAL This product is not suitable as a main heater...
Page 151: ...Kanuk GmbH Hauptstra e 131 01744 Dippoldiswalde 151 EN Kanuk Design Eco Design...