6.5.3 Ultra without KaControl module fitted, recirculating air
Automatically stop cooling operation when the maximum condensate level is reached to prevent the condensate tray from
overflowing.
Ultra cooling mode
Condensation pump
Ultra fan motor
Float switch
Cable with plug
Terminal block (external)
Mains power supply
to condensate pump
Alarm contact
Fig. 10: Wiring of the condensate pump
NC
C
PE
N
L
black
Condensation pump
Cable with plug
Mains power supply:
Voltage 230 V/ 50 Hz
Power consumption: 14 W
Fuse (by others): max. 16 A
Alarm contact:
Com and NC: Interruption of the power circuit as soon as the alarm level in the float module is
reached.
Voltage: max. 250 V
Switching current: max. 5 A
Terminal block (external)
grey
blue
brown
Fig. 11: Connection of the condensate pump