Ultra
Assembly, installation and operating instructions
30
7.1
Maximum electrical rating values
Electromechanical model
Type
Nominal
voltage [V]
Mains fre-
quency [Hz]
Active
power [kW]
Nominal
current [A]
Leakage cur-
rent [mA]
Maximum
pre-fusing
[A]
IP protec-
tion rating
Protection
class
73**58
230
50/60
0.14
1.27
<3.5
B10
54
I
84**58
230
50/60
0.14
1.27
<3.5
B10
54
I
85**58
230
50/60
0.17
1.51
<3.5
B10
54
I
96**58
230
50/60
0.46
2.13
<3.5
C16
54
I
96**56
230
50/60
0.46
2.13
<3.5
C16
54
I
Tab. 7: Electrical data, Ultra
Type
Number
Speed controller, type 30510
10
Room thermostat, type 30155
2
Clock thermostat 230 V, type 30256
2
Electronic speed controller, type 30515
10
Tab. 8: Maximum connectible unit heaters with EC fan per speed control unit
7.2
Electromechanical control
EMC-compliant installation of control cables
To avoid interference, ensure there is sufficient clearance between the mains power and control cables. When using a shiel-
ded cable, make sure that the shield is connected just on one side, i.e. only to the signal source with the protective earth (as
short and low inductance as possible)!
Fig. 13: Install the motor junction box.
Unscrew the screw in the bracket of the motor junction
box and remove the motor junction box from the area of
the intake crown.
Loosen screws in the cover of the motor junction box and
remove the cover.
Carry out the electrical wiring.
Commission the unit.
Close the motor junction box and refit it to the Ultra. As-
semble in reverse order to dismantling.
Important:
After completion of the electrical wiring, do
not push the cables through the motor guard close to the
fan!