Ultra
Assembly, installation and operating instructions
59
11
Faults
The following chapter describes possible causes of faults and the work needed to rectify them. Should faults occur frequently,
shorten the maintenance intervals in line with the actual loading on the unit.
Contact the manufacturer with any faults that cannot be rectified using the following information.
Behaviour in the event of faults
The following applies:
1. Immediately switch off the unit with faults that pose an immediate danger to persons or property!
2. Determine the cause of the fault!
3. Switch off the unit and prevent it from being reconnected if rectifying the fault requires work in the hazard area. Immedi-
ately advise a supervisor on site about the fault.
4. Either rectify the fault yourself or have it repaired by authorised personnel, depending on the nature of the fault.
The
provides information on who is authorised to rectify and remedy faults.
Status output via flash code
The EC fans are blockage protected. Protective functions that trigger an automatic shut-off in case of a fault are integrated.
These depend on the fan type.
3 x
2 x
ON
OFF
4 x
5 x
6 x
1 x
Viewing window for status LED
Fig. 39: Flash code
LED code
Relay in the fan*
Cause
OFF
0
No mains power
ON
1
Normal operation without faults
1x
1
No enable = OFF
2x
1
Temperature management active
4x
0
Phase failure (3 ~ types only)
5x
0
Motor blocked
6x
0
Power module fault
7x
0
Intermediate circuit, undervoltage
8x
0
Intermediate circuit, overvoltage
9x
1
Cool down phase, power module
11x
0
Fault, motor start
12x
0
Mains power too low
13x
0
Mains power too high