For electrical connection of the machine, a symmetric three-phase supply is necessary.
In a symmetrical three-phase supply the phase angles and voltages are all the same.
Incoming line within the switching cabinet to be as short as possible.
If external sensors or communications lines are to be connected to the machine, use shielded ca‐
bles and insert the same through EMC connections into the switching cabinet.
This machine may only be supplied from an earthed TN or TT three-phase supply in which
the neutral point is earthed.
The connection to an IT three-phase supply or a three-phase supply with one earthed phase
is not permitted.
Further information The wiring diagram in chapter 13.4 contains further details of the power supply connection.
2.14 Power supply specifications
Supply diameters and fusing (class gG) are selected according to DIN VDE 0100 part 430
(IEC 60364-4-43) and DIN VDE 0298-4:2013-06 if the following conditions are met:
■ multi-core copper conductors at an operating temperature up to 70 °C
■ Cable length <50 m
■ For an ambient temperature of 30 °C
■ Wiring type C, without cable contact
■ Current carrying capacity: Table 3 Column 11
(European Harmonisation Directive HD 60364-5-522011)
■ Bundled cables: Table 21
─ Single layer on wall or floor
─ Spacing ≥ outside diameter
➤ For other application conditions, check and determine the supply diameters according to
DIN VDE 0100 and DIN VDE 0298-4:2013-06 or the local energy provider.
Other conditions would include, for example:
■ Higher ambient temperature
■ Other cable installation method
■ Other bundled cables
■ Cable length >50 m
Further information The wiring diagram in chapter 13.4 contains further details of the electrical connection data.
2.14.1 Mains frequency: 50 Hz
Rated voltage: 200V / 3 / 50Hz
ASK 28
ASK 34
ASK 40
Backup fuse [A]
80
100
100
Supply cable [mm
2
]
4x25
4x35
4x35
Current drawn [A]
65
80
90
Tab. 26 Supply details 200V / 3 / 50Hz
2
Technical Specifications
2.14 Power supply specifications
12
Operating Manual Screw Compressor
ASK
901824 12 E
Summary of Contents for ASK 28
Page 2: ...Original instructions KKW SASK 2 22 en SBA SCHRAUBEN SC2IO KKW SSC 2 08 20170919 084918...
Page 6: ...Contents iv Operating Manual Screw Compressor ASK 901824 12 E...
Page 8: ...List of Illustrations vi Operating Manual Screw Compressor ASK 901824 12 E...
Page 138: ...13 Annex 13 4 Electrical Diagram 128 Operating Manual Screw Compressor ASK 901824 12 E...