The specified flow rate relates to the maximum available heat capacity.
➤ If required, enter your individual values in the prepared table.
➤ Consult KAESER SERVICE if you wish to use a different heat-receiving medium.
The primary side of the heat exchanger is connected to the cooling oil circuit of the machine.
The specifications refer to the secondary side of the heat exchanger.
Individual design data
My value
Heating from [°C]
Heating to [°C]
Temperature difference
(ΔT) [K]
Maximum available heat
output [kW]
(relative to ___ bar work‐
ing pressure)
Flow rate [m
3
/h]
Pressure drop [bar]
Tab. 34 Heat recovery: Individual design data
Component sprecification:
Feature
Value
Material
1.4401
Braze
Copper (Cu)
Max. working pres‐
sure [bar]
10
Minimum permissible in‐
let temperature [°C]
5
Max. permissible inlet
temperature* [°C]
45
Continuously possible
outlet temperature [°C]
70
Maximum permissible
outlet temperature [°C]
(Component limit value)
100
Maximum permissible
flow rate [m
3
/h]
8.7
Unsuitable cooling media
Salt water
Consult KAESER on the suitability of water.
* Consult KAESER about higher values.
Tab. 35 Specification: Heat exchanger (Option W2/W3)
2
Technical Specifications
2.15 Heat recovery
901824 12 E
Operating Manual Screw Compressor
ASK
15
Summary of Contents for ASK 28
Page 2: ...Original instructions KKW SASK 2 22 en SBA SCHRAUBEN SC2IO KKW SSC 2 08 20170919 084918...
Page 6: ...Contents iv Operating Manual Screw Compressor ASK 901824 12 E...
Page 8: ...List of Illustrations vi Operating Manual Screw Compressor ASK 901824 12 E...
Page 138: ...13 Annex 13 4 Electrical Diagram 128 Operating Manual Screw Compressor ASK 901824 12 E...