6.8 Parameter programming
Various operating parameters can be set in the programming
mode of Powador units.
The following parameters can be set:
Cut-off threshold of the overvoltage protector
–
Calibration of the line voltage
–
Calibration of the line current
–
Figure 6.13:
Jumper position to switch between
parameter mode and the normal
menu
Figure 6.14:
Jumper position in normal grid feed
mode (factory setting)
Figure 6.15:
Jumper position in programming mode
S e c t i o n 6 ·
I n s t a l l a t i o n a n d S t a r t - u p
Incorrect parameter settings will lead to a loss of
function, render your Safety Certifi cate [“Unbe-
denklichkeitsbescheinigung”] invalid, and result
in the loss of the safety functions.
Modifi cations may be made only in exceptional
cases and only after having consulted with the
manufacturer and the power supply company.
WARNING
DANGER
Disconnect the inverter from all power sources
before opening the housing.
ACTION
To switch to programming mode, a jumper (see fi gure 6.13)
must be switched.
Switch the jumper as shown in fi gure 6.15 to access the
display and programming modes.
ACTION
Close the unit again.
To switch to programming mode, press both keys (“1” and
“2”) at the same time. After approx. 2 seconds, the fi rst
confi guration parameter will appear on the display.
Use key “1” to scroll through the various menu items. The
menu is continuous. When you reach the end, the display
automatically returns to the fi rst item.
ACTION
Use key “2” to change the respective parameter. The
value then either increases or decreases, depending on
the parameter. The values here are also continuous, i.e.
after you reach the maximum value, they return to the
minimum value.