blueplanet hybrid 10.0
Page 26
In
ver
ter
NOTE
AC-side disconnection unit
› An AC-side disconnection unit must be provided during the final installation stage.
›This disconnector mechanism must be installed so that it can be accessed at any time without
obstruction.
› The grid connection leads (AC) must be protected with a four-pole circuit breaker type B 20A.
Tab. 3 Connecting the device to a standalone grid
Nominal voltage
230 V AC
Line protection
PE N L3 L2 L1 (switchable)
L1
L2
L3
N
PE
line frequency
Adjustable 45 to 65 Hz
Maximum power three-phase
9.99 kW
Maximum power single-phase 4.0 kW
7.3.2
Connecting the device for standby power operation
WARNING
Possible risk of fatal electric shock
This device may cause a current with a DC component. In standalone mode, an additional residual current
device (RCD) or a residual current monitor (RCM) of type B must be used on the supply side for protection
against direct or indirect contact.
WARNING
Possible risk of fatal electric shock
There must be no connection N and PE in the standby circuit. This is done by the hy-switch when
switching to standby power operation.
When installing the unit and the hy-switch, check the standby power circuit accordingly.
WARNING
Possible risk of fatal electric shock
Do not activate standby current generation if the connected grid is being serviced or has defects.
CAUTION
Transient voltage peaks can occur during rapid load changes in the standby power grid. Connected
devices must be able to withstand transients of up to 450 V or be protected against them accordingly.