blueplanet hybrid 10.0
Page 12
4
Technical data
4.1
General data
Fig. 3: KACO blueplanet hybrid 10.0 TL3 inverter
Features
of blueplanet hybrid 10.0 TL3
–
3-phase 10 kW hybrid inverter
–
2 integrated MPP trackers
–
Fast load regulation (<100 ms)
–
High efficiency: PV
Grid = >98%
PV
Battery = >97% Battery
Grid = >97%
–
Pure sinusoidal output voltage
–
Operation modes: Grid
operation, compensation mode,
standalone mode, standby
power operation
–
Aluminium housing
–
Convection cooling
–
All connections are plug-and-play
4.2
Detailed technical data
PV input (DC)
Efficiency
Max. recommended PV generator power
15000 W
PV (DC) to grid (AC) [max.]
>98.1 %
Number of inputs / MPP tracker
2
PV (DC) to grid (AC) [EU]
>97.8%
Nom./ max. DC voltage
680 V DC / 900 V DC
PV (DC) to battery (DC) [max.]
>98.8 %
Switch-on voltage
DC 240 V
Battery (DC) to grid (AC) [max.]
>97.7 %
MPP range@rated power
420 V DC - 740 V DC
Night consumption (off)
<0.1 W
Working range
200 V DC - 850 V DC
Idle consumption
<20 W
max. input power per MPP Tracker
12 A
Maximum short-circuit current I
sc max
15 A per input
Overload response
Operating point shift
Battery operation input (DC)
Battery operation AC connection
Nom. DC voltage
DC 425 V
Nominal charging power
9990 W
Max. charge and discharge current
25 A
Nominal discharge power
9990 W
Battery voltage Min. - Max.
96 V DC-450 V DC
Voltage waveform in standby current mode
true sine
Galvanic isolation
no
Number of phases
3
Protection
Fuse, cut-off relay
Grid supply (AC)
Efficiency
Nom. AC power
9 990 W
Grid frequency range
47.5 Hz-51.5 Hz
Max. AC power
11 000 VA
Power factor
0,9c -0,9i
Number of phases
3
Topology
Transformerless
Type. Power per phase on the grid
3 330 W
Load regulation
200 ms
Max. AC current per phase
16.1 A RMS
Power in standby mode (optional)
max. 4 000 W per phase
feed-in
sym. / asym.
and max. 10 000 W phase sum
Nom. AC voltage
210 - 264 V AC
Initial short-circuit alternating current (according to IEC
62109-2)
16.4 A
AC voltage range
184 - 264 V AC
Inrush current (according to IEC 62109-2)
1.7 A