Operating instructions
5.2.3
Automatic locking
LAVerI
The locking is bistable, e.g. the locking latch is held independently in the locked and unlo-
cked position. The locking state is not confirmed. Correct locking is not checked!
Door position
closed
locked
open
unlocked
moving
unlocked
closed
locked
manuallly unlocked
manually opened
LAveri
remains locked
remains unlocked
remains unlocked
is automatically locked upon manual clo-
sing
Behaviour in the event of a mains and battery failure:
Door position
closed
locked
open
unlocked
moving
unlocked
fail Safe
unlocked
Door remains closed.
unlocked
Door remains open.
unlocked
Door slows down to a full
stop.
Behaviour in the event of a mains and battery failure:
LAVeRI-fS
The locking mechanism is mono-stable, i.e. the locking hook is electrically maintained
only in one position, while it automatically drops into the other position in the event of a
mains failure. Whether the locking mechanism is locked or unlocked without mains power
is determined by the way in which the locking hook has been installed.
in function of the desired locking function, the fail Safe or fail Secure method must be
selected by means of the DiP Switch on the locking PCB.
fail Secure
remains locked
Door remains closed.
locked
After being manually
closed, the door is locked.
locked
Door slows down to a full
stop.
After being manually
closed, the door is locked.
Setting of the DiP switches on LAveri-fS:
see also wiring diagram (enclosed to the present instructions).
1
2
3
4 S103
Off On Off Off fail Safe without unlocking
On On Off Off fail Safe with unlocking
Off Off On On fail Secure with unlocking
Display of the error-LeD on LAveri-fS:
Off
everything Ok
On
incorrect setting of the DiP-Switch
flashing
please check the voltage