8 Programming
73
8.4.3 Scaling
The scaling start/end value and the dimen-
sion (unit) are defined to record the meas-
urement. For the alpha-numerical presenta-
tion of the measurement on the display and
on the chart, the number format is selected.
Example:
A temperature transmitter supplies a voltage
within the range of 0 — 10V. This range cor-
responds to a temperature of 200 — 600°C.
Programming:
Unit: °C
Scaling start:
200
Scaling end:
600
Number format:
XXX.X
Section 7.4
Display
Edit
Selection/input
with keys
Enter
Continue with
SCALING
E
3 SCALING
Select recording channel
h
,
R
E
2
2
3 DIMENSION: _ _ _ _
5 digits freely selectable
h
,
R
,
S
E
3
3
3 ZERO
+200.0 °C
Input start of scaling
h
,
R
,
l
,
r
,
S
E
4
4
3 FULL
+600.0 °C
Input end of scaling
h
,
R
,
l
,
r
,
S
E
Check
zero
<>
full
5
5
3 DECIMAL POINT:
x.xxx
Select decimal place :
AUTO, x.xxx, xx.xx, xxx.x,
xxxx.
h
,
R
E
h
forwards
R
backwards