8 Programming
67
Display
Edit
Selection/input
with keys
Enter
Continue with
5
(POTENTIO-
METER)
1 CHARACT.: linear
linear
X1
(customized lin. 1)
X2
(customized lin. 2)
h
,
R
E
customized X1
or X2:
10 (FILTER)
otherwise:
51
51
1 CONNECTION: 2/3-wire
2/3-wire
4-wire
Define type of potentio-
meter connection:
(2/3-wire circuit or 4-wire
circuit)
h
,
R
E
52
52
1 Ro:
+300.0 Ohm
Input start resistance
h
,
R
,
l
,
r
,
S
E
Check
0
≤
Ro
≤
3900 Ohm
53
53
1 Rp:
+900.0 Ohm
Input measurement
range (resistance Rp)
h
,
R
,
l
,
r
,
S
E
Check
0
≤
RANGE
≤
3900 Ohm
Total
resistance
Ro + Rp
≤
3900Ohm
min. span:
6 Ohm
10 (FILTER)
6
see table below!