Table 3: Medium temperature (Ex-data) model 406012/2-1
Not thermally insulated: the sensor is not surrounded by pipe insulating material.
Thermally insulated: the sensor is surrounded by pipe insulating material.
Special features of device version for operation in Ex-zone 1
Configuring the current output
For devices designed for use in Ex-zone 1, the current output configuration cannot be subsequently changed.
The desired configuration for the current output (active/passive) must be specified when the order is placed.
For the current output version (active/passive), see the identification marking in the device's terminal box.
Configuration of the digital outputs
For the device version for operation in Ex-zone 1, the digital outputs DO1 (51/52) and DO2 (41/42) can be configured for a connection to a NAMUR
switching amplifier. In the default setting, the outputs are configured with the standard wiring (non-NAMUR).
Devices with PROFIBUS-PA only feature the digital output DO2 (41/42).
IMPORTANT (NOTE)!
The standard version includes Ex-protection for gases and dust.
If the installation location for the device is classified as a potentially explosive area for gases and dust, the temperature data in the
"Gas & dust" columns in the table must be taken into consideration.
If the installation location for the device is only classified as a potentially explosive area for gases, the temperature data in the
"Gas" column in the table must be taken into consideration.
No
min
al wid
th
Te
mp
eratu
re c
lass
Ambient temperature
-20 °C to +40 °C
-20 °C to +50 °C
-20 °C to +60 °C
Not thermally insu-
lated
Thermally insulat-
ed
Not thermally insu-
lated
Thermally insulat-
ed
Not thermally insu-
lated
Thermally insulat-
ed
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
Gas
Gas &
dust
DN
10 to DN
1
00
T1 130 °C
110 °C
110 °C
110 °C
110 °C
T2 130 °C
110 °C
110 °C
110 °C
110 °C
T3 130 °C
110 °C
110 °C
110 °C
110 °C
T4 120 °C
110 °C
110 °C
110 °C
110 °C
T5 85 °C
85 °C
85 °C
85 °C
85 °C
T6 70 °C
70 °C
70 °C
70 °C
70 °C
DN1
25 to DN3
00
T1 130 °C
110 °C
110 °C
110 °C
110 °C
T2 130 °C
110 °C
110 °C
110 °C
110 °C
T3 130 °C
110 °C
110 °C
110 °C
110 °C
T4 125 °C
110 °C
110 °C
110 °C
110 °C
T5 90 °C
90 °C
90 °C
90 °C
90 °C
T6 75 °C
75 °C
75 °C
75 °C
75 °C
IMPORTANT (NOTE)!
This does not affect the output ignition protection type. The devices connected to these outputs must comply with the applicable
regulations for explosion protection.