5 Configuration
66
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
5.1.5
Monitoring
This allows an internal measurand to be monitored for compliance with limit
values.
Depending on the switching behavior, an overrange or underrange is output at
the digital output (option: relay or optocoupler).
Value / settings
Description
> Limit value moni-
toring
Switched off
No monitoring
Load voltage
These measurands can be monitored and are dependent on
the ordered device type.
Note:
If Power controller -> Thyristor control -> Logic (switch) and
Monitoring -> Limit value monitoring -> Load voltage, load
current, power (in W), or power (in kW) is selected,
the limit value monitoring only operates in the periods in which
the thyristors have been fired.
If the thyristors are blocked, as a general rule, the min. and
max. alarms are switched off.
Load current
Power (in W)
Power (in kW)
Resistance
Mains voltage
Device temperature
Min. limit value
alarm
0 to 9999.9
The absolute minimum limit values for load voltage, load cur-
rent, power, resistance, mains voltage, or device temperature
can be monitored.
If the measurand falls below this value, an error message ap-
pears at the bottom of the display and the yellow K1 LED
lights up. Depending on the set control direction, the digital
output switches as shown in the diagram.
The unit of the limit value corresponds to the measurand to be
monitored.
Max. limit value
alarm
0 to 9999.9
The absolute maximum limit values for load voltage, load cur-
rent, power, resistance, mains voltage, or device temperature
can be monitored.
If the measurand exceeds this value, an error message ap-
pears at the bottom of the display and the yellow K1 LED
lights up.
Depending on the set control direction, the digital output
switches as shown in the diagram.
The unit of the limit value corresponds to the measurand to be
monitored.
Summary of Contents for 709061/8-01-020
Page 16: ...1 Introduction 14 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 22: ...2 Mounting 20 V1 04 EN 00561071 Thyristor Power Switch TYA 201 TYA201 100A TYA201 150 200A ...
Page 23: ...V1 04 EN 00561071 Thyristor Power Switch TYA 201 21 2 Mounting TYA201 250A ...
Page 46: ...3 Electrical connection 44 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 56: ...4 Operation 54 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 78: ...5 Configuration 76 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 96: ...6 Special device functions 94 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 112: ...8 Error messages and alarms 110 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 120: ...10 Technical data 118 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 124: ...11 Certificates 122 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...