![JUMO 709061/8-01-020 Operating Manual Download Page 106](http://html.mh-extra.com/html/jumo/709061-8-01-020/709061-8-01-020_operating-manual_2031101106.webp)
8 Error messages and alarms
104
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Slave: limit.
active high temp.
Device temperature is higher than 105 °C.
Device too hot!
Output level is reduced.
(Limited power due to excess temperature)
- Ensure adequate ventilation or
provide for additional cooling
- Reduce load current
- Use power controller with high-
er maximum load current
Slave: supply volt.
too low
Mains voltage is not within specified toler-
ance range
v
Chapter 10.1 "Voltage supply, load
current"
Check nominal voltage of the device
type
v
Slave: supply volt.
too high
Mains voltage is not within specified toler-
ance range
v
Chapter 10.1 "Voltage supply, load
current"
Check nominal voltage of the device
type
v
Slave: Temp.drop in
mains voltage
Dangerous temporary equal proportion for
transformer loads has been detected.
v
Ensure stable mains supply.
Inhibit by
inhibit input
A firing pulse inhibit has been triggered via
a potential-free contact.
No power from the power controller.
v
Chapter 3.3 "Connection dia-
gram"
Open contact between terminal 7 and
8 at screw terminal X_2.
Inhibit by
ext. inhibit
The firing pulse inhibit has been triggered
via an interface.
v
Interface manual "Ext. inhibit"
Soft start phase
This message appears in the display until
the soft start has been completed.
v
Chapter 5.1.2 "Power controller"
Current limiting
active
The required output level causes an exces-
sive load current and is limited to the set
value.
v
Chapter 5.1.2 "Power controller"
Resistance
limitation active
The desired output level leads to current/
voltage values that exceed the set load re-
sistance. The output level is limited to the
admissible resistance to prevent overheat-
ing.
v
Chapter 5.1.2 "Power controller"
Error message
Cause
Remedy
Summary of Contents for 709061/8-01-020
Page 16: ...1 Introduction 14 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 22: ...2 Mounting 20 V1 04 EN 00561071 Thyristor Power Switch TYA 201 TYA201 100A TYA201 150 200A ...
Page 23: ...V1 04 EN 00561071 Thyristor Power Switch TYA 201 21 2 Mounting TYA201 250A ...
Page 46: ...3 Electrical connection 44 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 56: ...4 Operation 54 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 78: ...5 Configuration 76 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 96: ...6 Special device functions 94 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 112: ...8 Error messages and alarms 110 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 120: ...10 Technical data 118 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 124: ...11 Certificates 122 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...