5 Configuration
62
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
5.1.3
Analog inputs
The power controller has a voltage input and a current input.
These inputs (setpoint specification) specify the output to be provided by the
power controller at the load output.
In most cases, this signal is sent as a standard signal from an electronic con-
troller or PLC and is adjusted with these settings.
1.
Inverting analog inputs:
If, for example, the current measuring range start is set to 20 mA and the current measuring range end
is set to 0 mA, the power controller is switched off at 20 mA and switched on at 0 mA.
Value / settings
Description
Current measuring
range
0 to 20 mA
This setting specifies which current standard signal is con-
nected.
v
Chapter 3.3 "Connection diagram"
4 to 20 mA
Customer-specific
1
Current measuring
range, start
0 to 20 mA
Note: This parameter only appears if "Customer specific" is
set for the current measuring range (see above)!
Current measuring
range, end
0 to 20 mA
Note: This parameter only appears if "Customer specific" is
set for the current measuring range (see above)!
Voltage measuring
range
0 to 10 V
This setting specifies which voltage standard signal is con-
nected.
v
Chapter 3.3 "Connection diagram"
2 to 10 V
0 to 5 V
1 to 5 V
Customer-specific
1
Voltage measuring
range, start
0 to 10 V
Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!
Voltage measuring
range, end
0 to 10 V
Note: This parameter only appears if "Customer specific" is
set for the voltage measuring range (see above)!
k
/ bold = default setting
Summary of Contents for 709061/8-01-020
Page 16: ...1 Introduction 14 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 22: ...2 Mounting 20 V1 04 EN 00561071 Thyristor Power Switch TYA 201 TYA201 100A TYA201 150 200A ...
Page 23: ...V1 04 EN 00561071 Thyristor Power Switch TYA 201 21 2 Mounting TYA201 250A ...
Page 46: ...3 Electrical connection 44 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 56: ...4 Operation 54 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 78: ...5 Configuration 76 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 96: ...6 Special device functions 94 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 112: ...8 Error messages and alarms 110 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 120: ...10 Technical data 118 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 124: ...11 Certificates 122 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...