10 Technical data
116
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Altitude
≤
2000 m above MSL
Caution: At site altitudes > 1000 m above MSL, the ampacity of the power
controller decreases by 0.86 % per 100 m
Cooling
- Natural convection up to a load current of 200 A
- From 250 A of load current, forced convection
- At installation heights over 1000 m, the ampacity of the power controller de-
creases
v
Chapter 2.1.3 "Admissible load current depending on the ambient tem-
perature and the site altitude"
Fans (only for
type 709061/X-0X-250...)
Depending on the load voltage of the power controller, the fan terminal X14
must be supplied with the voltage specified below.
The lead protection must be between 2 A and a maximum of 5 A.
The fan is temperature-controlled, switches on automatically when the device
temperature reaches 85 °C, and remains in operation until the device tem-
perature falls below 70 °C.
Resistance to climatic con-
ditions
Rel. humidity
≤
85 % annual average, no condensation 3K3 according to
EN 60721
Installation position
Vertical
Test voltage
According to EN 50178 Tab. 18
Creepage distances
8 mm between mains voltage circuit and SELV circuits
For type 709061/X -0X-020...
12.7 mm between mains voltage circuit and SELV circuits
From type 709061/X -0X-032...
SELV = Separate Extra Low Voltage (safe low voltage)
Housing
Plastic, flammability class UL94 V0, color: cobalt blue RAL 5013
Power loss
The power loss can be calculated using the following empirical formula:
P
v
= 20 W + 1.3 V × I
Load
A
Maximum temperature of
the heat sink
110 °C
Weight
Load current 20 A approx. 1.1 kg
Load current 32 A approx. 2.1 kg
Load current 50 A approx. 2.7 kg
Load current 100 A approx.
3.8 kg
Load current 150 A approx.
8.5 kg
Load current 200 A approx.
9.5 kg
Load current 250 A approx.
10.2 kg
Standard accessories
1 operating manual
Load voltage of the power
controller
Tolerances
Fan specifications
Load voltage AC 24 V
-20 to +15 %, 48 to 63 Hz
AC 24 V/30 VA
Load voltage AC 42 V
-20 to +15 %, 48 to 63 Hz
Load voltage AC 115 V
-15 to +10 %, 48 to 63 Hz
AC 115 V/30 VA
Load voltage AC 230 V
-15 to +10 %, 48 to 63 Hz
AC 230 V/30 VA
Load voltage AC 265 V
Load voltage AC 400 V
Load voltage AC 460 V
Load voltage AC 500 V
Summary of Contents for 709061/8-01-020
Page 16: ...1 Introduction 14 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 22: ...2 Mounting 20 V1 04 EN 00561071 Thyristor Power Switch TYA 201 TYA201 100A TYA201 150 200A ...
Page 23: ...V1 04 EN 00561071 Thyristor Power Switch TYA 201 21 2 Mounting TYA201 250A ...
Page 46: ...3 Electrical connection 44 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 56: ...4 Operation 54 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 78: ...5 Configuration 76 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 96: ...6 Special device functions 94 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 112: ...8 Error messages and alarms 110 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 120: ...10 Technical data 118 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 124: ...11 Certificates 122 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...