8 Error messages and alarms
102
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Limiting active
high temperature
Device temperature is higher than 105 °C.
Device is too hot, output level is reduced!
(Limited power due to excess temperature)
- Ensure adequate ventilation or
provide for additional cooling
- Reduce load current
- Use power controller with high-
er maximum load current
Mains voltage is
too low
Mains voltage is not within specified toler-
ance range
v
Chapter 10.1 "Voltage supply, load
current"
Check nominal voltage of the device
type
v
Mains voltage is
too high
Mains voltage is not within specified toler-
ance range
Chapter 10.1 "Voltage supply, load cur-
rent"
Check nominal voltage of the device
type
Temporary
drop in mains volt-
age
Dangerous temporary equal proportion for
transformer loads has been detected.
v
Ensure stable mains supply.
Master-slave
rotary field error
Counterclockwise rotary field has been de-
tected
v
Master-slave
wiring is wrong.
Wiring fault has been detected
Rotary field detec-
tion failed
Rotary field detection not possible
- Check connection
v
Chapter 3.3 "Connection dia-
gram"
- Eliminate mains disturbances
Wire break
Current input
Input current too small for the selected
measuring range.
- Check wiring for wire breaks and
reverse polarity.
- Check upstream devices (con-
trollers)
Wire break
Voltage input
Input voltage too small for the selected
measuring range.
- Check wiring for wire breaks and
reverse polarity.
- Check upstream devices (con-
trollers)
Malfunction
Bus error
No connection to the Profibus master
Check wiring and master device (PLC).
Master-slave
Error in comm.
Error in the data transfer between master
and slave
Is the 1:1 patch cable plug connected
correctly?
Data cable
faulty
Communication between master and slave
interrupted.
Check the 1:1 patch cable and replace,
if necessary
Synchronization
failed
Slave device switched off or communica-
tion between master and slave interrupted
Check plug connection of 1:1 patch
cable or voltage supply
Error message
Cause
Remedy
Summary of Contents for 709061/8-01-020
Page 16: ...1 Introduction 14 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 22: ...2 Mounting 20 V1 04 EN 00561071 Thyristor Power Switch TYA 201 TYA201 100A TYA201 150 200A ...
Page 23: ...V1 04 EN 00561071 Thyristor Power Switch TYA 201 21 2 Mounting TYA201 250A ...
Page 46: ...3 Electrical connection 44 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 56: ...4 Operation 54 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 78: ...5 Configuration 76 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 96: ...6 Special device functions 94 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 112: ...8 Error messages and alarms 110 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 120: ...10 Technical data 118 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Page 124: ...11 Certificates 122 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...