23
6 Operation
6.4
Parameter
6.4.1
Input
6.4.2
Analog output
Parameter
Display
Setting range
1
Pressure unit
bar
kPa
MPa
psi
mbar
Note:
The units kPa and mbar cannot be configured for
all measuring ranges.
Offset
(zero-point correction)
-20.00 ... 0.00 ... +20.00% of the measuring range
Note:
Automatic offset correction See section 7.5
"Setting the zero point (offset) (Off.P)", page 31.
Damping
(filter time constant)
0.00 ... 99.99 s
Parameter
Display
Setting range
1
Signal type
(for analog output)
4 ... 20 mA
0 ... 20 mA
0 ... 10 V
Scaling start
(for analog output)
0.00 ... 75.00% of nominal measuring range
Scaling end
(for analog output)
25.00 ... 100% of nominal measuring range
Signal for error
(for analog output)
3.4 mA or 22 mA for output signal 4...20 mA
0 mA or 22 mA for output signal 0...20 mA
0 V or 10.7 V for output signal 0...10 V
Note:
Depending on the configured output signal.
1
The default setting is marked in bold.