7 Commissioning
42
7.16 Setting the display unit (D.Uni)
Setting range:
Uni.P = pressure unit set as for "Uni.P", See section 7.4
"Selecting the unit of the measured value (Uni.P)", page
28.
Pro2 = percentage of scaled measuring range = "Sc.Hi"
minus "Sc.Lo", See section 7.8.1 "Setting the starting
value of scaling (Sc.Lo)", page 35 and See section 7.8.2
"Setting the final value of scaling (Sc.Hi)", page 36.
Factory setting:
std
Setting
✱
Unlock the instrument, See section 7.2 "Unlocking the instrument (code
entry)", page 27.
✱
"Rotate" until the bottom line shows "D.Uni".
✱
"Press"
Uni.P = the measured value is displayed in the unit that was selected, See
section 7.4 "Selecting the unit of the measured value (Uni.P)", page
28.
or
Pro.2 = the measured value is displayed as a percentage of the scaled
measuring range, See section 7.8.1 "Setting the starting value of
scaling (Sc.Lo)", page 35 and See section 7.8.2 "Setting the final
value of scaling (Sc.Hi)", page 36.
Example
The measuring range of the instrument was set to from -50 to +350 mbar and
the scaled measuring range is 300 mbar.
If the instrument measures a pressure of +150 mbar, 50% is displayed.