11 Instrument description
11.1 Technical data
General
Reference conditions
DIN 16086 and EN 60770
Sensor system
Construction
Pressure transfer
medium
Permissible load change
Silicon sensor with stainless steel separating diaphragm
Synthetic oil, FDA-compliant
more than 10 million
Location
Mounting location
Calibration location
Location-dependent
zero point offset
- Basic type extension
000 (standard design)
- Basic type extension
004 (for elevated
medium temperature)
Any
Device standing vertically, process connection on bottom
Zero point correction possible locally or via setup (20% of nominal
measuring range)
≤
1 mbar
≤
10 mbar
Display
Type
Alignment
Size
Color
Switching state indicator
Measuring unit
Backlit LCD
Display can be rotated 180° (via setup)
Housing can be turned 320° (mechanically)
Display field 16x26 mm / font size 7 mm / 2 x 4 places
Normal operation:amber
Error:
red
Setup mode:
red
K1, K2
mbar, bar, kPa, MPa, psi, %
Operation
Local
via setup
With accompanying combination tool or screwdriver 0.5x3
Pin 12 of the M12 round plug