Wärtsilä JOVYTEC PNT 1000VA
–
3000VA BAX 3313_en
- 13 -
4.4
3000 VA
Output power
cos
0,7 ind.
3000VA / 2100W
Network supply
Voltage
230V
Input voltage ranges
168V - 276V (0-100% load)
140 - 159V (0-70% load)
120 - 139V (0-40% load)
Current with standard charger
10,7A
Current with additional charger
11,9A
Frequency
50Hz ±3Hz or 60Hz ±3Hz
Phase
Single phase
Power Factor
0,98
External fuse protection
D01/16A
Battery
(installed in battery pack inside the ups)
Direct current link voltage
72V
Backup time
6min. at
100% load
8min. at
80% load
14min.at 50%
load
Type
Maintenance free, closed lead acid batteries
Charging time
< 8 hours for 90% recharge
Output
Voltage
230V Standard (208V / 220V / 240V selectable
at the panel)
Frequency
Automatic adjustment via of the ups
Power factor
cos
0,7 ind.
Phase
Single phase
Distorsion factor
< 3% at linear load
Overload behaviour
100 to 125% for 60 seconds
125
–
150% for 10s
Crest Factor
3 : 1
Efficiency
AC to AC
88 - 98% according to the operation mode
Switch over behaviour
Power failure
0ms
Overload switching
Automatic overload switching by the ups
Noise level
At an distance of 1m
< 50dB(A)
Compass Distances
Standard
Reserve
Environment
Protection Degree
IP 21
Temperature
0°C to 45°C
+15 … +25°C (recommended)
Air humidity
0% to 95%, non condensing
Storage at …
20°C (recommended) with Battery
-20°C to 50°C without Battery
Applied Rules
Operation Mode VFI SS 111 acc. to IEC
62040-3,
DIN EN 60945
Interfaces
RS 232-Interface
Optional:
USB Interface
Relay card
AS/400 - Adapter
SNMP - Adapter
Supports power management and diagnosis
such as BATTERY LOW, UPS ON/OFF
Software is compatible with operating systems
such as: Windows 95/98/NT/2000/XP, Novell,
Unix, etc current operating systems.
Dimensions
UPS Device
Width
225mm
Depth
425mm
Heights
360mm
Weight UPS
approx. 17 kg
Weight UPS incl. Battery
approx. 33 kg
Scope of delivery
Hardware/Software
UPS unit
Manual BAX 3313E
Interface cable, Mounting plate and fixing
screws with distance washer
Software UPSMON