Replacing an internal UPS battery
UPS units of this series
offer the possibility by replacing the battery during operation. One must ensure in this
case that the UPS unit is running in normal mode and not in autonomy mode. Proceed as follows to replace the
battery:
1.
Remove the display panel through the stripping of the plastic cover. For that you seize please under the
plastic covering on the front and the hold clip press up. You move at the press up hold clips the covering
under gentle pressure forward.
2.
Unhook the display panel. The fastening clip is located at the top side of the covering.
3.
Remove the fastening screw on the retaining bracket using a Phillips screwdriver. The fastening screw on
the retaining bracket is located on the left side of the battery rack.
4.
Unhook the retaining bracket.
5.
Pull the battery pack out of the UPS unit using the pulling strap.
Please note that if a power failure
occurs now the load will not be supplied with power.
6.
Open the battery pack using a Phillips screwdriver by removing the cross-head screws in the upper and
downer area of the battery pack.
7.
You can now replace the batteries.
8.
Screw the battery pack together again using the cross-head screws.
9.
Push the battery pack into the battery shaft of the UPS unit.
10. Insert the retaining bracket and secure with the cross-head screw.
11. Hook display panel onto the right side of the UPS unit into the retaining tang.
12. Press on display panel evenly until it engages.
13. Conduct a manual battery test to check the battery.
Please note that when conducting the battery test
faulty insertion of the battery could mean that the load is not taken over and this will lead to power
consumer crashes.