Wärtsilä JOVYTEC PNT 1000VA 

 3000VA   BAX 3313_en

- 23 -

 

7.3 

Configuration 

Use of the function display and the function keys allows diverse settings to be made on the UPS unit. The 
formalism is as follows: 

In order to achieve Configuration Mode it is necessary to press the key 

FUNC

 for 2 seconds. The first 

configuration parameter appears in the display. 

The key 

FUNC

 is used to manoeuvre through the parameters. 

The key 

ENTER

 is used to select the parameter point to be altered. 

The key 

FUNC

 is used to move through the options for the selected parameter. 

The key 

ENTER

 is used to confirm the selected option and the display readout: 

Save ?

 appears before 

hand 

Saving is achieved by pressing the key 

ENTER 

again. 

7.4 

Table of the adjustable parameters 

Adjustable 

parameter 

Indication in 

the display 

Explanation 

Selections 

for 

parameter 

Factory 

setting 

Adjusting the output voltage 

O/P V adjustment 

Nominal voltage 

208/220/ 
230/240V 

230V 

Setting the 
input frequency tolerance 

I/P Freq. Adjustment 

Frequency tolerance in 
unsynchronised mode 

± 2% 
± 5% 
± 7% 

± 5% 

Setting of the tolerance of the bypass 
voltage 

I/P bypass adjustment 

Voltage tolerance 

± 10% 
+10/-15% 
+15/-20% 

+10/-15% 

Free Run Mode 

Free-Run-Set 

Unsynchronised mode 

ON/OFF 

ON 

Bypass activation/deactivation in Free 
Run Mode 

Free

Run-Mode

If activated the UPS will switch 
to bypass if the preset 
parameters are not maintained 

ON/OFF 

OFF 

Operating mode setting 

HE mode setting 

Online/Offline mode 

ON/OFF 

OFF 

Setting for a permanent manual bypass  Man. bypass setting 

Activate manual bypass (only 
for servicing)* 

ON/OFF 

OFF 

Load management 

Load segment setting 

Segment 1 ON/OFF 
Segment 2 ON/OFF 

ON/OFF 

ON 

Performing a battery test 

Manual battery test 

Battery test 
Battery OK. 
Battery not OK. 

ON/OFF 

OFF 

Quiet functioning 

Alarm acoustic 

Activate, deactivate the 
acoustic alarm 

ON/OFF 

OFF 

Number of battery cabinets 

No. of ext. batteries 

Setting number of battery 
packs for the autonomy 
calculation; a maximum of 2 

1 - 2 

Dependent on 
the required 
backup time 

Reversal polarity protection 

Phase reversal setting 

Activation, deactivation 
of phase reversal 

ON/OFF 

OFF 

Language selection 

Language 

Language selection 

English 
German 
French 
Spanish 
Italian 

German 

Generator mode 

Generator 

Generator mode** 

ON/OFF 

OFF 

Setting RS 232 interface 

COM control command 

Setting of RS232 interface 

ON/OFF 

ON 

*) 

The manual bypass function should always be switched off since for a switched on manual bypass the load in the case of a 
power failure cannot be supplied by the UPS. 

**) 

The UPS should we switched off and then switched on again before the generator is switched. 

P L E A S E   N OT E! 

If  the  selected  option  is  not  stored  within  10  seconds  then  the  value  is  reset 
automatically and the menu goes bank into its normal condition. 

Summary of Contents for Wartsila JOVYTEC PNT 1000 VA

Page 1: ...Operating Manual Uninterruptible Power Supply W rtsil JOVYTEC PNT 1000VA 3000VA BAX 3313_en...

Page 2: ...008 A Heller DNV Certificate added 7 29 08 2008 Th Harms 08 308 Relay card removed Not possible at NT Series 8 23 03 2009 A Heller 09 149 Battery Security Data Sheet added 9 26 03 2010 A Heller 10 113...

Page 3: ...the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating m...

Page 4: ...0 VA 1500 VA 16 5 3 FRONT VIEW 2000 VA 3000 VA 17 5 4 REAR VIEW 2000 VA 3000 VA 18 6 ELECTRICAL CONNECTION 18 6 2 COMMISSIONING 20 6 3 UPS SHUT DOWN 20 7 OPERATING AND INDICATING ELEMENTS 21 7 1 FUNCT...

Page 5: ...INFORMATION 28 9 REMOTE MONITORING 28 9 1 CONNECTING THE UPS TO THE COMPUTER 28 9 2 ASSIGNMENT OF THE RS232 INTERFACE 28 10 SPECIAL EQUIPMENT 29 10 1 ELECTRONIC STOP FUNCTION 29 11 BATTERY 30 11 1 BA...

Page 6: ...lems the reliability of the systems is our major goal since over 60 years of experience in secured power supply and techniques The scope of this manual is to describe briefly the parts that constitute...

Page 7: ...al discharging voltage is not reached 1 2 General notes regarding the ups devices The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE reg...

Page 8: ...tion During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating vo...

Page 9: ...means that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault i...

Page 10: ...over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 45dB A Compass Distances Standard 600mm Reserve 450mm Environment Protectio...

Page 11: ...n mode Switch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 50dB A Compass Distances Standard 600mm Reserve 400mm Environ...

Page 12: ...tch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 50dB A Compass Distances Standard 600mm Reserve 400mm Environment Prote...

Page 13: ...10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an dist...

Page 14: ...Data Voltage 12V Capacity 7Ah Quantity 3 pcs Weigth each bloc 2 54kg Dimensions each bloc LxWxH 151 x 65 x 94mm Type of battery JL 205670 Battery for 2000VA UPS General Data Voltage 12V Capacity 7Ah...

Page 15: ...nt view 1000VA 1500 VA Sign Meaning ON Operation ON LINE Output Voltage available ON BAT Battery Operation BYPASS Bypass Operation FAULT UPS Failure Remark for mounting JT1000 1500 please use the cros...

Page 16: ...SPEISUNG 230V 50 60Hz MAINS INPUT 230V 50 60Hz SHOCK MOUNT L1 PE Schwingmetallpuf f er SHOCK MOUNT Abdeckplatte UPS OUTPUT 2 230V 50 60Hz COVER PLATE RS232 EARTHING BOLT M6 02 Abdeckplatte Schwingmeta...

Page 17: ...C FAULT SHOCK MOUNT BYPASS SHOCK MOUNT ON BAT ON LINE ON MOUNTING PLATE 5 3 Front view 2000 VA 3000 VA Sign Meaning ON Operation ON LINE Output Voltage available ON BAT Battery Operation BYPASS Bypass...

Page 18: ...Hz IN SHOCK MOUNT EPO N SHOCK MOUNT N RS232 USV AUSGANG 2 230V 50 60Hz NETZEINSPEISUNG 230V 50 60Hz Abdeckplatte COVER PLATE Schwingmetallpuf f er Abdeckplatte COVER PLATE 10 AMP X2 02 PE Eingangssich...

Page 19: ...f the ups 3 Set in the battery connector For transport or shipment of the ups device this connector has to be removed to prevent short circuit or fire while improper transport 4 All connecting up work...

Page 20: ...proceed as follows Switch off all consumers Press the ON OFF button in the front panel for 3 seconds An acoustic sound bleep is emitted while pressing the ON OFF button and the message Switching off s...

Page 21: ...et a parameter such as the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER but...

Page 22: ...50 2Hz Input frequency of the UPS BAT VOLT 24V Battery voltage of the battery pack O P LOAD 80 Utilisation of the UPS as a percentage O P W 700W Output in Watts O P VA 1000VA Output in VA O P CURR 2A...

Page 23: ...de If activated the UPS will switch to bypass if the preset parameters are not maintained ON OFF OFF Operating mode setting HE mode setting Online Offline mode ON OFF OFF Setting for a permanent manua...

Page 24: ...point to be altered using the key ENTER in this case HE mode The key FUNC is then used to manoeuvre through the options for the selected parameter ON OFF You have the option to select between 10 and 1...

Page 25: ...t frequency range covers the range of 45Hz 65Hz The following situation occurs where the UPS unit has a fault Before the UPS unit switches to bypass the CPU first checks to see whether the input volta...

Page 26: ...ult yourself using these trouble shooting instructions The UPS emits acoustic error signals for A mains fault the UPS unit runs in battery mode and the alarm sounds every 5 seconds Battery discharge u...

Page 27: ...red Battery operation on battery A bleep every 5 sec The UPS operates in autonomy mode loss of input mains Save your data and shut down your computer in a controlled fashion Battery charge fault charg...

Page 28: ...e UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer...

Page 29: ...ug Actuation of the external electronic STOP switch causes the output of the UPS unit to be switched to voltage free and the UPS unit shuts down In order to provide the consumers with a voltage again...

Page 30: ...he case of restoration of the mains power before the end of the backup time the inverter continues to run automatically until the battery is charged up Restoration of mains power after total discharge...

Page 31: ...acket is located on the left side of the battery rack 4 Unhook the retaining bracket 5 Pull the battery pack out of the UPS unit using the pulling strap Please note that if a power failure occurs now...

Page 32: ...battery The ventilation slots front and backsides of the UPS have to be clean without any dust or something soiling to prevent a reduced air exchange Please observe the necessary distance to surround...

Page 33: ...st blich Not scalable drawing Detail General tolerances Treatment Material Material thickness Surface treatment Varnishing Tool metal bender Prog no metal bender A 1 2 3 4 5 6 7 8 A B B C C D D O B k...

Reviews: