background image

Wärtsilä JOVYTEC PNT 1000VA 

 3000VA   BAX 3313_en

- 7 -

 

N O T E! 

The UPS should be attached to the mains supply and switched on at the latest 4 
weeks after receipt in order to prevent the battery discharging itself. 

P L E A S E   N O T E

In order to exclude the possibility of overloading or constant switching over to bypass 
due  to  consumer  generated  non-sinusoidal  current  peaks,  no  devices  such  as  laser 
printers, fax machines as well as devices operating with a similar technology should be 
connected to the UPS. 
In  cases  where  it  is  essential  that  such  devices  be  operated  then  a  UPS  must  be 
selected whose capacity can match the maximum possible current peaks. 
Devices  with  power  reduction  due  to  half  wave  power  consumption,  (e.g.  coffee 
machines, hair dryers) can lead to immediate destruction of the power-output stage. The 
battery is not galvanically isolated from the mains so occurrence of a mains voltage at 
the battery terminals is possible! The UPS unit does not have an output transformer and 
is therefore not galvanically isolated from the mains!! 

P L E A S E   N O T E! 

The  batteries  used  are  just  designed  for  the  required  backup  time  to  supply 
the nominal load of the UPS. Operation of the UPS unit in free running mode 
for a longer period of time on battery can damage the batteries. This effect is 
due  to  the  nature  of  the  battery  since  for  a  longer  discharge  period  the  final 
discharging voltage is not reached. 

1.2 

General notes regarding the ups devices 

The device may only be opened by trained specialists. 

The system is to be connected up and earthed according to VDE regulations. Provisions of the local  energy 

supply company must be observed.

The ventilation slits on the front and rear sides must not be covered and a distance from the wall of at least 

100 mm

 is essential. 

The UPS unit is built according to Protection Class 

IP 21

 and is designed for installation in heated internal 

spaces (at 20°C). A lower operating temperature lowers the bridging time. 

No devices with a connecting cable in excess of 

10 metres

 in length should be connected to the UPS. This 

measure serves to ensure observance of the EMC standard. 

No alterations should be made to the UPS unit. The warranty will expire in cases of inappropriate physical 
interventions. 

2. 

Description of the System 

UPS  devices  of  this  type  are  particularly  suited  for  supplying  critical  power  consumers  in  industry  and  the 
office  such  as  personal  computer,  computer-controlled  devices,  PLCs  and  similar  equipment.  The  output 
voltage  is  sinusoidal.  In  normal  cases  the  attached  consumers  are  supplied  with  power  from  the  installed 
rectifier and installed inverter from the mains  power supply network (online operation).  Any disturbances in 
the  mains  such  as  voltage  peaks,  voltage  drops,  harmonic  distortions  or  noises  etc.  are  filtered  out.  The 
installed battery is constantly being charged up by means of a charging rectifier with  a charge preservation 
charging stage which is gentle on the batteries. 

Summary of Contents for Wartsila JOVYTEC PNT 1000 VA

Page 1: ...Operating Manual Uninterruptible Power Supply W rtsil JOVYTEC PNT 1000VA 3000VA BAX 3313_en...

Page 2: ...008 A Heller DNV Certificate added 7 29 08 2008 Th Harms 08 308 Relay card removed Not possible at NT Series 8 23 03 2009 A Heller 09 149 Battery Security Data Sheet added 9 26 03 2010 A Heller 10 113...

Page 3: ...the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating m...

Page 4: ...0 VA 1500 VA 16 5 3 FRONT VIEW 2000 VA 3000 VA 17 5 4 REAR VIEW 2000 VA 3000 VA 18 6 ELECTRICAL CONNECTION 18 6 2 COMMISSIONING 20 6 3 UPS SHUT DOWN 20 7 OPERATING AND INDICATING ELEMENTS 21 7 1 FUNCT...

Page 5: ...INFORMATION 28 9 REMOTE MONITORING 28 9 1 CONNECTING THE UPS TO THE COMPUTER 28 9 2 ASSIGNMENT OF THE RS232 INTERFACE 28 10 SPECIAL EQUIPMENT 29 10 1 ELECTRONIC STOP FUNCTION 29 11 BATTERY 30 11 1 BA...

Page 6: ...lems the reliability of the systems is our major goal since over 60 years of experience in secured power supply and techniques The scope of this manual is to describe briefly the parts that constitute...

Page 7: ...al discharging voltage is not reached 1 2 General notes regarding the ups devices The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE reg...

Page 8: ...tion During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating vo...

Page 9: ...means that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault i...

Page 10: ...over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 45dB A Compass Distances Standard 600mm Reserve 450mm Environment Protectio...

Page 11: ...n mode Switch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 50dB A Compass Distances Standard 600mm Reserve 400mm Environ...

Page 12: ...tch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 50dB A Compass Distances Standard 600mm Reserve 400mm Environment Prote...

Page 13: ...10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an dist...

Page 14: ...Data Voltage 12V Capacity 7Ah Quantity 3 pcs Weigth each bloc 2 54kg Dimensions each bloc LxWxH 151 x 65 x 94mm Type of battery JL 205670 Battery for 2000VA UPS General Data Voltage 12V Capacity 7Ah...

Page 15: ...nt view 1000VA 1500 VA Sign Meaning ON Operation ON LINE Output Voltage available ON BAT Battery Operation BYPASS Bypass Operation FAULT UPS Failure Remark for mounting JT1000 1500 please use the cros...

Page 16: ...SPEISUNG 230V 50 60Hz MAINS INPUT 230V 50 60Hz SHOCK MOUNT L1 PE Schwingmetallpuf f er SHOCK MOUNT Abdeckplatte UPS OUTPUT 2 230V 50 60Hz COVER PLATE RS232 EARTHING BOLT M6 02 Abdeckplatte Schwingmeta...

Page 17: ...C FAULT SHOCK MOUNT BYPASS SHOCK MOUNT ON BAT ON LINE ON MOUNTING PLATE 5 3 Front view 2000 VA 3000 VA Sign Meaning ON Operation ON LINE Output Voltage available ON BAT Battery Operation BYPASS Bypass...

Page 18: ...Hz IN SHOCK MOUNT EPO N SHOCK MOUNT N RS232 USV AUSGANG 2 230V 50 60Hz NETZEINSPEISUNG 230V 50 60Hz Abdeckplatte COVER PLATE Schwingmetallpuf f er Abdeckplatte COVER PLATE 10 AMP X2 02 PE Eingangssich...

Page 19: ...f the ups 3 Set in the battery connector For transport or shipment of the ups device this connector has to be removed to prevent short circuit or fire while improper transport 4 All connecting up work...

Page 20: ...proceed as follows Switch off all consumers Press the ON OFF button in the front panel for 3 seconds An acoustic sound bleep is emitted while pressing the ON OFF button and the message Switching off s...

Page 21: ...et a parameter such as the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER but...

Page 22: ...50 2Hz Input frequency of the UPS BAT VOLT 24V Battery voltage of the battery pack O P LOAD 80 Utilisation of the UPS as a percentage O P W 700W Output in Watts O P VA 1000VA Output in VA O P CURR 2A...

Page 23: ...de If activated the UPS will switch to bypass if the preset parameters are not maintained ON OFF OFF Operating mode setting HE mode setting Online Offline mode ON OFF OFF Setting for a permanent manua...

Page 24: ...point to be altered using the key ENTER in this case HE mode The key FUNC is then used to manoeuvre through the options for the selected parameter ON OFF You have the option to select between 10 and 1...

Page 25: ...t frequency range covers the range of 45Hz 65Hz The following situation occurs where the UPS unit has a fault Before the UPS unit switches to bypass the CPU first checks to see whether the input volta...

Page 26: ...ult yourself using these trouble shooting instructions The UPS emits acoustic error signals for A mains fault the UPS unit runs in battery mode and the alarm sounds every 5 seconds Battery discharge u...

Page 27: ...red Battery operation on battery A bleep every 5 sec The UPS operates in autonomy mode loss of input mains Save your data and shut down your computer in a controlled fashion Battery charge fault charg...

Page 28: ...e UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer...

Page 29: ...ug Actuation of the external electronic STOP switch causes the output of the UPS unit to be switched to voltage free and the UPS unit shuts down In order to provide the consumers with a voltage again...

Page 30: ...he case of restoration of the mains power before the end of the backup time the inverter continues to run automatically until the battery is charged up Restoration of mains power after total discharge...

Page 31: ...acket is located on the left side of the battery rack 4 Unhook the retaining bracket 5 Pull the battery pack out of the UPS unit using the pulling strap Please note that if a power failure occurs now...

Page 32: ...battery The ventilation slots front and backsides of the UPS have to be clean without any dust or something soiling to prevent a reduced air exchange Please observe the necessary distance to surround...

Page 33: ...st blich Not scalable drawing Detail General tolerances Treatment Material Material thickness Surface treatment Varnishing Tool metal bender Prog no metal bender A 1 2 3 4 5 6 7 8 A B B C C D D O B k...

Reviews: