Wärtsilä JOVYTEC PNT 1000VA
–
3000VA BAX 3313_en
- 29 -
10.
Special equipment
10.1
Electronic STOP function
The UPS is fitted with an integrated electronic STOP function. This function is
deactivated as standard via a bridge at the rear of the UPS unit. If the electronic
STOP functionality is to be used then the bridge should be removed on the plug
and an external switch (opener) clamped to the rear plug. Actuation of the
external electronic STOP switch causes the output of the UPS unit to be
switched to voltage-free and the UPS unit shuts down. In order to provide the
consumers with a voltage again the electronic STOP switch must be reset and
the UPS restarted. There is still a
voltage
inside and at the terminals even after
the electronic STOP function was activated.
Electronic STOP
P L E A S E N O T E!
The following conversion work or extension to the unit may only be performed by
trained personnel and with the UPS unit in a deenergised condition.
Observe the relevant safety regulations!!