23
installaton guide
www.jouleuk.co.uk
4.7.1 ELECTRICAL HEATING MODE
In this operating mode, the electric booster heater is the only heat
appliance used. The water temperature can be set to between 30 °C
and 70 °C.
4.7.2 “HEAT PUMP” OPERATING MODE
Water heating is only guaranteed when the inlet air temperature is be-
tween -10 °C and 35 °C. Selecting this operating mode means that the
heat pump is the only heat appliance used . The water temperature can
be set to between 30 °C and 60 °C. At very low temperatures, the frost
protection function is activated .
4.7.3 “COMBI” OPERATING MODE
In this operating mode, two heat appliances are used depending on
the situation: the heat pump or the electric booster heater. The water
temperature can be set to between 30 °C and 70 °C. If the water tem-
perature in the cylinder below 60 °C and the inlet air temperature is
between -10 °C and 35 °C, the heat pump is the only heat appliance
used . Otherwise, the electric booster heater is switched on .
4.8 “SET” SUBMENU - SETTINGS
You can set various parameters in the “Set” submenu:
• Date
• Prog - Operating times
• Leg - Legionella
• Duct - use of ducts
• Purg - Drain
• Fset - Default settings
20
ENG
Installation and user manual
4.7.1 ELECTRICAL HEATING MODE
In this operating mode, the electric booster heater is the only heat appliance
used. The water temperature can be set to between 30 °C and 70 °C.
4.7.2 “HEAT PUMP” OPERATING MODE
Water heating is only guaranteed when the inlet air temperature is between
-10 °C and 35 °C. Selecting this operating mode means that the heat pump is
the only heat appliance used. The water temperature can be set to between
30 °C and 60 °C. At very low temperatures, the frost protection function is
activated.
4.7.3 “COMBI” OPERATING MODE
In this operating mode, two heat appliances are used depending on the
situation: the heat pump or the electric booster heater. The water temperature
can be set to between 30 °C and 70 °C. If the water temperature in the
cylinder below 60 °C and the inlet air temperature is between -10 °C and 35
°C, the heat pump is the only heat appliance used. Otherwise, the electric
booster heater is switched on.
4.8 “SET” SUBMENU - SETTINGS
You can set various parameters in the “Set” submenu:
•
Date
•
Prog - Operating times
•
Leg - Legionella
•
Duct - use of ducts
•
Purg - Drain
•
Fset - Default settings
20
ENG
Installation and user manual
4.7.1 ELECTRICAL HEATING MODE
In this operating mode, the electric booster heater is the only heat appliance
used. The water temperature can be set to between 30 °C and 70 °C.
4.7.2 “HEAT PUMP” OPERATING MODE
Water heating is only guaranteed when the inlet air temperature is between
-10 °C and 35 °C. Selecting this operating mode means that the heat pump is
the only heat appliance used. The water temperature can be set to between
30 °C and 60 °C. At very low temperatures, the frost protection function is
activated.
4.7.3 “COMBI” OPERATING MODE
In this operating mode, two heat appliances are used depending on the
situation: the heat pump or the electric booster heater. The water temperature
can be set to between 30 °C and 70 °C. If the water temperature in the
cylinder below 60 °C and the inlet air temperature is between -10 °C and 35
°C, the heat pump is the only heat appliance used. Otherwise, the electric
booster heater is switched on.
4.8 “SET” SUBMENU - SETTINGS
You can set various parameters in the “Set” submenu:
•
Date
•
Prog - Operating times
•
Leg - Legionella
•
Duct - use of ducts
•
Purg - Drain
•
Fset - Default settings
20
ENG
Installation and user manual
4.7.1 ELECTRICAL HEATING MODE
In this operating mode, the electric booster heater is the only heat appliance
used. The water temperature can be set to between 30 °C and 70 °C.
4.7.2 “HEAT PUMP” OPERATING MODE
Water heating is only guaranteed when the inlet air temperature is between
-10 °C and 35 °C. Selecting this operating mode means that the heat pump is
the only heat appliance used. The water temperature can be set to between
30 °C and 60 °C. At very low temperatures, the frost protection function is
activated.
4.7.3 “COMBI” OPERATING MODE
In this operating mode, two heat appliances are used depending on the
situation: the heat pump or the electric booster heater. The water temperature
can be set to between 30 °C and 70 °C. If the water temperature in the
cylinder below 60 °C and the inlet air temperature is between -10 °C and 35
°C, the heat pump is the only heat appliance used. Otherwise, the electric
booster heater is switched on.
4.8 “SET” SUBMENU - SETTINGS
You can set various parameters in the “Set” submenu:
•
Date
•
Prog - Operating times
•
Leg - Legionella
•
Duct - use of ducts
•
Purg - Drain
•
Fset - Default settings
20
ENG
Installation and user manual
4.7.1 ELECTRICAL HEATING MODE
In this operating mode, the electric booster heater is the only heat appliance
used. The water temperature can be set to between 30 °C and 70 °C.
4.7.2 “HEAT PUMP” OPERATING MODE
Water heating is only guaranteed when the inlet air temperature is between
-10 °C and 35 °C. Selecting this operating mode means that the heat pump is
the only heat appliance used. The water temperature can be set to between
30 °C and 60 °C. At very low temperatures, the frost protection function is
activated.
4.7.3 “COMBI” OPERATING MODE
In this operating mode, two heat appliances are used depending on the
situation: the heat pump or the electric booster heater. The water temperature
can be set to between 30 °C and 70 °C. If the water temperature in the
cylinder below 60 °C and the inlet air temperature is between -10 °C and 35
°C, the heat pump is the only heat appliance used. Otherwise, the electric
booster heater is switched on.
4.8 “SET” SUBMENU - SETTINGS
You can set various parameters in the “Set” submenu:
•
Date
•
Prog - Operating times
•
Leg - Legionella
•
Duct - use of ducts
•
Purg - Drain
•
Fset - Default settings