15
installaton guide
www.jouleuk.co.uk
2.1 SAFETY, CONTROL AND PROTECTION DEVICES
2.1.1 HIGH PRESSURE SWITCH
If the operating pressure is outside of the recommended range, the
pressure switch switches off the appliance and displays a fault.
2.1.2 HIGH LIMIT SAFETY CUT-OUT
The high limit safety cut-out ensures that the water temperature in the
cylinder does not exceed the prescribed limit . If the temperature limit
is exceeded, the DHW heating shuts down . The reset is performed
manually by a certified contractor.
2.1.3 TEMPERATURE SENSOR FOR AIR INLET
The temperature sensor measures the temperature of the inlet air in the
evaporator . If the measured value is outside the operating temperature
range, DHW heating automatically switches from the “Combi” operat-
ing mode to “Electric booster heater” . If the appliance is in the “Heat
pump” operating mode, DHW heating is interrupted until the tempera-
ture returns to within the permissible range .
2.1.4 PRESSURE RELIEF VALVE
The safety valve should be opened regularly to remove calcium build-
up and to verify that it is not blocked .
2.1.5 PRESSURE REDUCING VALVE
The system must include a pressure reducing valve if the main line
pressure is above 5 bar . The pressure reducing valve must be installed
in the main line . A pressure of 3 to 4 bar is recommended .
INSTALLATION DIAGRAM
12
ENG
Installation and user manual
Safety of electrical appliances for domestic use and similar purposes
The following requirements apply in accordance with EN 60335-1 in order to prevent hazards from occurring
when using electrical appliances: “This appliance may be operated by children aged 8 or over and by people with
full physical, sensory and mental capabilities who have the necessary training and experience to use this type of
appliance. They must be supervised or instructed on how to use the appliance safely and on the associated risks.
Children must not play with the appliance. Children must not clean or service the appliance without supervision.”
“Damaged power cables must be replaced by the manufacturer, the service department or a qualified contractor in
order to prevent hazards.”
2.1 SAFETY, CONTROL AND PROTECTION DEVICES
2.1.1 HIGH PRESSURE SWITCH
If the operating pressure is outside of the recommended range, the pressure switch switches off the appliance and
displays a fault.
2.1.2 HIGH LIMIT SAFETY CUT-OUT
The high limit safety cut-out ensures that the water temperature in the cylinder does not exceed the prescribed limit.
If the temperature limit is exceeded, the DHW heating shuts down. The reset is performed manually by a certified
contractor.
2.1.3 TEMPERATURE SENSOR FOR AIR INLET
The temperature sensor measures the temperature of the inlet air in the evaporator. If the measured value is outside
the operating temperature range, DHW heating automatically switches from the “Combi” operating mode to “Electric
booster heater”. If the appliance is in the “Heat pump” operating mode, DHW heating is interrupted until the
temperature returns to within the permissible range.
2.1.4 PRESSURE RELIEF VALVE
The safety valve should be opened regularly to remove calcium buildup and to verify that it is not blocked.
2.1.5 PRESSURE REDUCING VALVE
The system must include a pressure reducing valve if the main line pressure is above 5 bar. The pressure reducing
valve must be installed in the main line. A pressure of 3 to 4 bar is recommended.
INSTALLATION DIAGRAM