Installation
Indications,
functions and options
Messages
Operation and function
If a malfunction occurs, the display symbols will indicate an error code:
T2A fuse
°C
ȍ
°C
ȍ
-10
961
55
1213
-5
980
60
1232
0
1000
65
1252
5
1019
70
1271
10
1039
75
1290
15
1058
80
1309
20
1078
85
1328
25
1097
90
1347
30
1117
95
1366
35
1136
100
1385
40
1155
105
1404
45
1175
110
1423
50
1194
115
1442
Resistance values of
Pt1000 sensors
The symbol
is indicated on the display and the symbol
ISmASHING
Sensor fault. An error code instead of a temperature is shown on the sensor
display channel.
Disconnected Pt1000 temperature sensors can be checked with an ohmmeter.
Please check the resistance values correspond with the table.
Cable is broken. Check the cable.
Short circuit. Check the cable.
- 88.8
888.8
Operating control LED is permanently off.
Check the power supply of the controller. Is it disconnected?
no
The fuse of the controller could be
blown. The fuse holder (which holds
the spare fuse) becomes accessible
when the cover is removed.The fuse
can then be replaced.
yes
Check the supply line and recon-
nect it.
6 Troubleshooting