en
6
Installation
Indications,
functions and options
Messages
Operation and function
2.2 Electrical connection
WARNING!
Electric shock!
Upon opening the housing, live parts are exposed!
Î
Always disconnect the device from power supply before
opening the housing!
ATTENTION! ESD damage!
Electrostatic discharge can lead to damage to electronic compo-
nents!
Î
Take care to discharge properly before touching the in-
side of the device!
Note:
Connecting the device to the power supply must always be the last step
of the installation!
Note:
It must be possible to disconnect the device from the mains at any time.
Î
Install the mains plug such that it is accessible at any time.
Î
If this is not possible, install a switch that can be accessed.
Do not use the device if it is visibly damaged!
4HEPOWERSUPPLYOFTHEDEVICEMUSTBEx6^x(Z !TTACHmEXIBLE
cables to the housing with the enclosed strain relief and the corresponding screws.
The controller is equipped with 1 semiconductor relay to which a load such as a
pump, a valve, etc. can be connected:
• Relay 1
18 = Conductor R1
17 = Neutral conductor N
13 = Grounding terminal
The
mains connection
is at the following terminals:
19 = Neutral conductor N
20 = Conductor L
12 = Grounding terminal
The terminals marked
PWM
ARECONTROLOUTPUTSFORAHIGHEFlCIENCYPUMP
7 = PWM -
8 = PWM +
Speed control of a HE pump is possible via a PWM signal. The pump has to be con-
nected to the relay as well as to the PWM output of the controller. Power supply
to the HE pump is effected by switching the relay on or off.
VBus
®
IP 20
T2A
220 ... 240 V~
50-60 Hz
Temp. Sensor Pt1000
S1
S2
S3
PWM
R1
VBus
1
2
3
4
5
6
7
8
9 10
12 13 14
15 16 17 18 19 20
N
N
L
R1 1 (1) A 220 ... 240 V~
DeltaSol BS HE
mains terminals
Fuse
load terminals
sensor terminals
grounding
terminals
Connect the
temperature sensors
(S1 to S3) to the corresponding terminals
with either polarity:
1 / 2 = Sensor 1 (e. g. collector sensor)
3 / 4 = Sensor 2 (e. g. store sensor)
5 / 6 = Sensor 3 (e. g. store sensor top)
2.3 Data communication / Bus
The controller is equipped with the
VBus
®
for data transfer and energy supply
to external modules. The connection is to be carried out at the terminals marked
VBus
(any polarity).
One or more
VBus
®
modules can be connected via this data bus, such as:
• DL2 Datalogger
• DL3 Datalogger
Furthermore, the controller can be connected to a PC or integrated into a network
via the VBus
®
/USB or VBus
®
/LAN interface adapter (not included).
Note:
More accessories on page 20.