en
16
Installation
Indications,
functions and options
Messages
Operation and function
Maximum speed
nMX
Maximum speed
Adjustment range: 22 … 100 %
Factory setting: 100 %
A relative maximum pump speed can be allocated to the PWM output via the
adjustment channel
nMX
.
Minimum speed
nMN
Minimum speed
Adjustment range: 20 … 98 %
Factory setting: 30 %
A relative minimum pump speed can be allocated to the PWM output via the ad-
justment channel
nMN
.
Operating mode
MAN
Operating mode
Adjustment range: OFF, AUtO, ON
Factory setting: AUtO
For control and service work, the operating mode of the relay can be manually ad-
justed. For this purpose, select the adjustment channel
MAN
in which the following
adjustments can be made:
Operating mode
OFF : Relay off
mASHING
Auto : Relay in automatic operation
ON : Relay off
mASHING
Note:
Always adjust the operating mode back to
AUtO
when the control and
service work is completed. Normal operation is not possible in manual
mode.
Language
LANG
Language selection
Selection: dE, En
Factory setting: dE
In this adjustment channel the menu language can be selected.
• dE : Deutsch
• En : English