Jøtul GF 200 DV IPI Installation And Operation Instructions Manual Download Page 8

8

139587_05  GF 200 DV IPI  October 2015

Vent Restriction

The GF 200 DV IPI  is equipped with an Exhaust Restrictor 

Plate which enables you to regulate the flow of exhaust 

gas. The plate prevents overly strong draft that can 

cause poor combustion and weak flame picture. 

Follow 

the guidelines below, and on the following pages, to 

determine the correct restrictor plate setting for your 

particular installation configuration.

Exhaust Restrictor

The Exhaust Restrictor is an adjustable shutter located 

within the firebox exhaust outlet. It is adjusted by moving 

a pivot pin from the factory-set, fully OPEN (no restriction) 

to fully CLOSED, (full restriction ). The Minus and Plus 

signs on the dial relate to degrees of restriction, from less 

to more. See Fig. 8. The five lettered positions correlate to 

the termination zones (A,B,C,D,E) diagramed in figure 9. 

Use the diagram to determine the degree of restriction 

and shutter setting you should use. 

 

Adjusting Exhaust Restrictor Plate:  

1.   Use the Vent Termination Matrix to determine which 

setting position to use.

2.  Lift the Top Plate from the stove.
3.  Locate the restrictor adjustment dial on the top of the 

exhaust outlet. Use a 1/4” nut driver to loosen the lock 

nut and pivot the dial to the position appropriate to 

your termination zone.  See figs. 8 and 9.

4.  Tighten the lock nut and replace the Top Plate.

Venting Requirements

The Jøtul GF 200 DV IPI  gas stove may be installed with 

a vertical or horizontal termination and must conform to 

the configuration requirements described below.

This appliance is approved for use with vent systems 

from the following manufacturers: 

•  M&G DuraVent, Inc.  (Direct Vent Pro Series)   

•  American Metal Products (Amerivent) 

•  Security Chimneys International, Ltd. (Secure Vent) 

•  Selkirk Metalbestos (Direct Temp) 

•  Metal-Fab, Inc. (Direct Vent) 

•  Industrial Chimney Corp.  (ExcelDirect) 

•    Bernard Dalsin Mfg. (Pro Form)

Use parts of one manufacturer only - DO NOT MIX 

VENT COMPONENTS FROM DIFFERENT MANUFACTURERS 

IN THE SAME SYSTEM.

Installation of any components not manufactured 

or approved by Jøtul or failure to meet all clearance 

requirements will void all warranties and could result in 

property damage, bodily injury, or serious fire.

The approved vent configurations described 

in this manual are derived from extensive testing 

under controlled laboratory conditions. Gas appliance 

performance can be negatively affected by variables 

present in the installation environment, i.e: atmospheric 

pressure, strong prevailing winds, adjacent structures and 

trees, snow accumulation, etc. These conditions should be 

taken into consideration by the installer and stove owner 

when planning the vent system design. 

IMPORTANT

•  JOINT SEALING REQUIREMENT:  

APPLY A 1/8” BEAD OF HIGH-

TEMPERATURE SEALANT 

OR MIL-PAC® TO THE MALE 

SECTION OF THE INNER VENT 

PIPE.  THE CEMENT SHOULD 

FORM A SEAL BETWEEN THE 

INNER AND OUTER PIPES.

•  NEVER MODIFY ANY 

VENTING COMPONENT, 

OR USE ANY DAMAGED 

VENTING PRODUCT.

•  THE GAS APPLIANCE AND 

VENT SYSTEM MUST BE 

VENTED DIRECTLY TO THE 

OUTSIDE OF THE BUILDING AND NEVER ATTACHED TO 

A CHIMNEY SERVING A SOLID FUEL OR GAS BURNING 

APPLIANCE.  EACH DIRECT VENT GAS APPLIANCE MUST 

HAVE ITS OWN SEPARATE VENT SYSTEM.  COMMON 

VENT SYSTEMS ARE PROHIBITED.   

•  IF VENTING SYSTEM IS DISASSEMBLED FOR ANY 

REASON, REINSTALL PER THE INSTRUCTIONS PROVIDED 

FOR THE INITIAL INSTALLATION.

Figure 7.

Approved Horizontal  

and Vertical Vent Terminations

•  Up to four 45° or two 90° elbows are permitted 

in addition to the starter elbow. A horizontal run, 

however, must be reduced by 5 feet for each additional 

elbow, whether 45° or 90°.

 

NOTE: Long vent runs (over 12 ft.) in uninsulated air 

space may require operation in CPI mode for best 

performance.

•  ALL VENTING MUST TERMINATE (END) WITHIN ONE OF 

THE DESIGNATED AREAS.

•  SET STOVE EXHAUST RESTRICTOR TO THE POSITION 

THAT CORRESPONDS TO THE VENT TERMINATION 

AREA IN THE MATRIX. When termination is exactly 

on a division line, use the less restrictive position. 

For example, if termination is at 11 ft./3ft., restriction 

should be set at Position D.

The circled letter designations in the vent matrix in 

figure 9 correspond to the Exhaust Restrictor dial settings 

on the stove.  First, determine which vent termination 

zone is appropriate for your installation, then adjust the 

restrictor to the corresponding position as shown in figure 9.

Summary of Contents for GF 200 DV IPI

Page 1: ...department Installation and service must be performed by a qualified installer service agency or the gas supplier In the Commonwealth of Massachusetts a carbon monoxide CO detector shall be installed...

Page 2: ...ed by code Tee joint Pipe wrench Pipe sealant 10 mm open end wrench 1 2 7 16 open end wrench Phillips head screwdriver Flat head screwdriver 1 4 nut driver Gloves Safety glasses Torx T 20 screwdriver...

Page 3: ..._________ INSTALLER __________________________________ FUEL TYPE ____________________________________ FUEL CONVERSION NO _______ YES______ INTALLATION DATE _____________________________ INSTALLATION T...

Page 4: ...ORE BEGINNINGTHE INSTALLATION 2 SAFETY BARRIER SCREEN This appliance is equipped with a Certified Barrier Screen that must be installed before operating the unit It is secured to the shipping pallet R...

Page 5: ...ation Code current edition DO NOT OPERATE THIS STOVE IF ANY PART HAS BEEN UNDER WATER Call a qualified service technician to inspect the heater and to replace any part of the con trol system and any g...

Page 6: ...tly on carpeting vinyl linoleum or wood laminate flooring such as Pergo If this appliance will be installed on any combustible material OTHER THAN WOOD a floor pad must be in stalled that is either me...

Page 7: ...5 5 5 Max Mantel Depth Min Mantel Depth Max Top Trim Depth 1 3 5 Max 6 1 2 A 51 1 2 in 1308 mm B 50 in 1270 mm C 48 1 2 in 1232 mm D 47 in 1194 mm Figure 4 Minimum Alcove Clearances Figure 2 Parallel...

Page 8: ...or failure to meet all clearance requirements will void all warranties and could result in property damage bodily injury or serious fire The approved vent configurations described in this manual are d...

Page 9: ...re 8 Use 1 4 socket driver to loosen the Exhaust Restrictor dial and adjust as appropriate for your termination zone Figure 9 Vent Termination Zone Matrix NG LP NOTE 4 6 VENT MAXIMUM RUN DIRECTLY OFF...

Page 10: ...ly for your particular installation See also figs 10 12 Figure 11 Remove the Primary Baffle from Secondary Baffle Secondary Baffle Primary Baffle Secondary Baffle Use Fig 11 Fuel Termination Vent Inst...

Page 11: ...t of the vent may alleviate these conditions Use Wall Straps to support an offset pipe run at intervals of three feet to avoid excessive stress on the offsets Elbows Four 45 or two 90 elbows may be us...

Page 12: ...PIPE MUST EXTEND 6 FEET BEYOND THE DAMPER AREA OF THE FIREPLACE If the intake flex duct does not extend the full length of the chimney and connect to both the unit and the termination cap A METAL BLO...

Page 13: ...t pipe Use 4 6 Vent Adaptor Kit 157674 See figs 13 14 Use the guidelines for vertical termination shown on page 11 In masonry chimney a fireclay liner or listed steel liner must be present the entire...

Page 14: ...rance from projections exceeding 2 1 2 See fig 24 Wall Cut out Opening A minimum 10 X 10 250 mm x 250 mm square hole is required for proper pipe clearances through a combustible wall DO NOT FILL AIR S...

Page 15: ...a height 15 ft above the meter regulator assembly I Clearance to service regulator vent outlet 3 ft 91 cm J Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any...

Page 16: ...change back for use with natural gas WARNING THE CONVERSION KIT IS TO BE INSTALLED BY AN AUTHORIZED J TUL SERVICE TECHNICIAN IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTION AND ALL CODES AND REQUIRE...

Page 17: ...om its brass elbow housing and replace with the appropriate orifice supplied in the kit 10 Replace the Burner Plate Engage the burner tube with the Air Shutter assembly Be sure the burner is level and...

Page 18: ...leaks using a soapy water solution Never use an open flame to check for leaks Leak test 1 Mix a 50 50 solution of water and dish soap 2 Light appliance see lighting instructions on the inside back co...

Page 19: ...2000 feet Check with your gas supplier before performing derate adjustment to the burner If the gas supplier does not derate fuels install High Altitude Adjustment Kit 157675 for Propane and Kit 15767...

Page 20: ...ermostat 750003 Use only a 750 millivolt DC two wire circuit wall thermostat with this appliance The thermostat should be placed in the same room as the heater typically 5 feet off the floor Avoid dra...

Page 21: ...uld be spread sparsely over the burner plate and around the logs Use a pencil to position the stones so as not to block the burner plate porting TO INSURE PROPER BURNER FUNCTION DO NOT OBSTRUCT THE PI...

Page 22: ...lot flame should be steady not lifting or floating The flame should be blue in color around the pilot hood with traces of yellow toward the outer edges The pilot flame should engulf the top 1 8 of the...

Page 23: ...used by incomplete combustion in the flames and lack of combustion air entering the air shutter opening To adjust the air shutter 1 Reach under the stove and loosen the wingnut See fig 45 Slide the wi...

Page 24: ...HE GLASS PANEL REMOVED CRACKED OR BROKEN REPLACEMENT OF THE GLASS SHOULD BE DONE BY A LICENSED OR QUALIFIED SERVICE PERSON USE ONLY REPLACEMENT GLASS PROVIDED BY YOUR AUTHORIZED J TUL DEALER NEVER SUB...

Page 25: ...de of the rear shroud See fig 48 1 Set the Burner switch to OFF Open the main gas supply line to the stove 2 Connect the AC DC Power Adaptor to the terminal on the back of the DFC board bracket See fi...

Page 26: ...ent should be vacuumed annually to remove any dust and debris Use a soft brush attachment and handle the logs carefully as they are fragile Vacuum more frequently if there are pets in the home The pil...

Page 27: ...rness 3 Control Box 4 Snapstat Bracket 5 Rheostat Knob 6 Snapstat 7 M6 Flange Nuts 2 8 M6 x 12 Hex Bolts 2 9 8 x 1 2 Sheet metal screw 4 Tools Required 1 4 socket driver 10 mm socket driver or wrench...

Page 28: ...ally adjusted with the rheostat knob If the burner turns off the blower will be shut off automatically as the stove cools down If automatic blower circulation is not desired place the blower control s...

Page 29: ...ntact your local officials about installation restrictions and requirements in your area THIS APPLIANCE MAY BE INSTALLED AS AN OEM INSTALLATION IN A MANUFACTURED MOBILE HOME AND MUST BE INSTALLED IN A...

Page 30: ...6 Left Door n a n a 7 Right Door n a n a Front Assembly 15592392 156384 includes Front Doors and Hinge Pins 13 Safety Barrier 157688 n a 8 Hinge Pin 4 125960 9 Fender Washer M6 4 120004 10 Bolt M6 x 2...

Page 31: ...Pole 77 Series 13 22093192 Control Door GF 200 DV IPI 14 221185 Orifice 1 20 mm 225441 Orifice 2 1mm 15 222280 Gasket Drop in Orifice Holder 16 222292 Elbow 90 deg Brass 3 8 NTP x 3 8 dia flare Figur...

Page 32: ...Wing Nut M6 Zinc 10 225092 Air Deflector Burner Skirt 11 225439 Pilot Shield High Wind Optional Kit 157685 12 225438 Pilot Shield 13 224785 Pilot NG LP Dual Fuel Convertible Flame Hood 14 118218 Screw...

Page 33: ...157685 No Part No Description 1 22136592 Glass Frame II 2 129124 Gasket Tadpole 25 dia x 1 25 6 ft 3 220576 Glass Panel Ceramic 4 220042 Replacement Glass Clips 5 155599 Replacement Glass Kit GF 200 D...

Page 34: ...ined in this owner s manual or local and or national fire and building regulations 3 Damage due to service performed by an installer service agency or gas supplier unless otherwise agreed to in writin...

Page 35: ...replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING 1 Set the thermostat to the lowest setting 2 Turn off...

Page 36: ...installation it is important that these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specifi cation color...

Reviews: