
20
139587_05 GF 200 DV IPI October 2015
Optional Brick Panel Kit
157666
1. Lift the Top Plate from the stove.
2. Disengage the two compression latches from the glass
frame at the top of the firebox and pull the glass frame
up and out of the stove.
3. Locate the retainer tabs in the upper corner of each
side of the firebox. Bend each retainer tab out enough
to engage the side brick panels. See fig. 36.
4. Install the Lower Panel.
Position it up against the back wall, resting on the
burner skirt.
5. Set the Upper Panel on the Lower Panel. Hold the rear
panels in place while setting the Left Side Panel under
its retainer tab and against the wall. Bend the retainer
down to fully engage the side panel.
6. Engage the Right Side Panel under its retainer tab and
seat it against the wall. Bend that retainer tab down to
secure the panel in place.
Retainer Tab
Figure 36. Install the Brick Panels.
Optional Wall Thermostat
750003
Use only a 750 millivolt DC two-wire circuit wall
thermostat with this appliance. The thermostat should
be placed in the same room as the heater, typically 5
feet off the floor. Avoid drafty areas or any area that may
affect the accuracy of the thermostat.
The thermostat should be connected to the
terminal block using a minimum of 16 gauge wire with a
maximum length of 25 feet of wire.
Connect the two thermostat wire leads to the
terminals on the block located to the left of the valve. Do
not overtighten the connections.
IT IS NOT NECESSARY
TO DISCONNECT ANY OTHER WIRES.
See Figs. 37 and 48.
For thermostatic operation, set the On/Off/Stat
switch to the Stat position. Set the pilot mode to either
IPI or CPI.
At the thermostat, the two wires should be
connected to the two connection screws on the
thermostat base plate per the manufacturer’s
instructions.
CAUTION:
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
THE CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER OR
DANGEROUS OPERATION. ALWAYS VERIFY PROPER OPERATION
AFTER SERVICING THE APPLIANCE.
Figure 37. Accessory wiring diagram.